Adjustments, Continued), How to change a setting – Winco ASCO 300 D Design 30-230 Amp User Manual
Page 13
ADJUSTMENTS
(continued)
4--2
Do not make any setting changes
while the controller is energized.
!
How to Change a Setting
1. Prevent the transfer switch from operating by discon-
necting one source first, then the other, as follows:
a.
If the transfer switch is in the Normal position,
open the emergency source circuit breaker. Turn
the engine starting control to off. Then open the
normal source circuit breaker.
b.
If the transfer switch is in the Emergency
position, open the normal source circuit breaker.
Turn engine starting control to test or run. Then
open the emergency source circuit breaker.
2. Disconnect both harness plugs from controller by
squeezing the latches. Do not pull on the wires.
3. Remove cover from the controller by releasing latch
on right side with your thumb. See Figure 4-1.
4. Locate the appropriate adjustment potentiometer or
DIP switch for the setting that you want to change.
Refer to Table 4-1 and Table 4–2 on page 4-1 and
Figure 4-2, Figure 4–3, Figure 4–4 on page 4–2.
5. Use a small screwdriver to turn the potentiometer
clockwise to increase the time delay or counterclock-
wise to decrease it. See Figure 4-3.
6. Use a ball-point pen (or similar pointed tool) to slide
the switch actuators left or right so they match the il-
lustration next to the setting (left = off, right = on).
Recheck the setting. See Figure 4-4.
7. Install the cover on the controller by hooking it on
the left side and latching the right side.
8. Reconnect both harness plugs to the controller by
aligning and pressing straight in until latches click.
Close the enclosure door.
!
9. Close the enclosure door, then restore both sources:
a.
If the transfer switch is in the Normal position
first close the normal source circuit breaker,
then close the emergency source circuit breaker.
b.
If the transfer switch is in the Emergency
position, close the normal source circuit breaker.
The load will be automatically retransferred to
the normal source. Then close the emergency
source circuit breaker.
10. Turn the engine starting control to automatic.
thumb
latch
cover
hook on
left side
Figure 4-1. Controller cover latch.
9 volt
alkaline
battery
battery
on/off
jumper
retransfer
to normal
time delay
transfer to
emergency
time delay
harness
plugs
S3 DIP
switch
S1 DIP
switch
S2 DIP
switch
P1
P2
J5
Figure 4-2. Location of potentiometers,
DIP switches, battery, and battery jumper.
P1 or P2
potentiometer
clockwise to
increase
counterclockwise
to decrease
Figure 4-3. Changing time delay potentiometers.
DIP
switches
SW1
SW2
SW3
actuator
on
off
(8 on each DIP switch)
Figure 4-4. Setting DIP switch actuators.