SECTION 3 TESTING & SERVICE

3--1

PREVENTIVE MAINTENANCE

Reasonable care in preventive maintenance will insure

high reliability and long life for the automatic transfer

switch.

Operate the switch at least once a month. Perform this

four step Electrical Operation Test. This is a test with

load transfer.

Press until light

FLASHES

Press for 15 Seconds

TRANSFER SWITCH TEST

BYPASS TIME DELAY SET ENGINE EXERCISER

Transfer Switch Test

1. Press and hold the door-mounted

TRANSFER

SWITCH TEST button until the engine starts and

runs. This should happen within 15 seconds.

2. The transfer switch will operate to the Emergency

position. If the

Transfer To Emergency Delay is

used, the transfer will occur after a time delay

(up to 5 minutes). For immediate transfer press

BYPASS TIME DELAY button.

3. The Transfer Switch will operate back to the

Normal position after the

Retransfer To Normal

Delay (up to 30 minutes). For immediate

retransfer press

BYPASS TIME DELAY button.

4.

Unloaded Running (Engine Cooldown) Delay

allows engine to run unloaded for 5 minutes.

Clean and inspect the switch once a year. De-energize all

sources, then brush and vacuum away any excessive dust

accumulation. Remove the transfer switch barriers and

check contact condition. Replace contacts when pitted or

worn excessively. Reinstall the barriers carefully.

Maintain transfer switch lubrication. The transfer switch

has been properly lubricated, and under normal operat-

ing conditions no further lubricating is required. Renew

factory lubrication if the switch is subjected to severe dust

or abnormal operating conditions. Relubricate the

operator if TS coil is replaced. Order lubrication

625550–001 (Castrol EndurexR 4000 lubricant).

Replacement parts. Replacement parts are available in

kit form. When ordering parts provide the Serial No. and

Catalog No. from the transfer switch nameplate. Contact

your local ASCO Power Technologies sales office or ASI.

In the United States call 1–800–800–ASCO (2726), or in

Canada call 1–888–234–ASCO (2726).

DISCONNECTING THE CONTROLLER

The harness disconnect plugs are furnished for repair

purposes only and should not have to be unplugged. If the

controller must be isolated, follow these steps carefully.

Disconnecting the Plugs

Do not unplug the controller until step

1a. or 1b. below is completed.

!

1. Observe the position of the transfer switch.

a. If the transfer switch is in the Normal position, place

standby engine starting control in the off position.

Then open the emergency source circuit breaker.

b. If the transfer switch is in the Emergency position,

open the normal source circuit breaker. Place the

engine starting control in the test or run position.

2. Separate the quick disconnect plugs by squeezing the

latches. Do not pull on the harness wires.

3. Label, remove, and tape the signal wires connected

to the engine start terminals on the transfer switch:

TB1 and TB3, or TB1 and TB2.

Reconnecting the Plugs

Do not reconnect the controller until step

1a. or 1b. and 2 below are completed.

!

1. Observe the position of the transfer switch.

a. If the transfer switch is in the Normal position, be

sure that the standby engine starting control is still

in the off position. The emergency source circuit

breaker still should be open.

b. If the transfer switch is in the Emergency position,

normal source circuit breaker still should be open.

2. Reconnect the signal wires connected to the

appropriate engine start terminals on the transfer

switch. See Section 1, Engine Starting Contacts.

3. The harness plugs and sockets are keyed. Carefully

align the plugs with the sockets and press straight in

until both latches click.

4. Restore the opposite source as follows:

a. If the transfer switch is in the Normal position,

place the standby engine starting control in the

automatic

position. Then close the emergency

source circuit breaker.

b. If the transfer switch is in the Emergency position,

close the normal source circuit breaker. The load will

be automatically retransferred to the normal source

after the Retransfer to Normal Delay. For immediate

retransfer, press BYPASS TIME DELAY button.

Place the engine starting control in the automatic

position.