6.7.3 ENGINE RUNNING
Once the engine is running, the Warm Up timer, if selected, begins, allowing the engine to stabilise before
accepting the load.
Load will be automatically transferred from the mains supply to the generator.
NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This prevents
excessive wear on the engine.
In test mode, the set will continue to run on load until either:
•
The stop button
is pressed – The set will stop immediately or after off load cooling run depending
upon configuration.
•
The auto button
is pressed. The set will observe all auto mode start requests and stopping timers
before beginning the Auto mode stopping sequence.