DSE7200 / 7300 Series Operators Manual
39
4.2.9 RS485 CONNECTOR
NOTE:- RS485 connector is not fitted to the 7200 series controller.
PIN No
NOTES
A +
Two core screened twisted pair cable.
120Ω impedance suitable for RS485 use.
Recommended cable type - Belden 9841
Max distance 1000m (1km) when using Belden 9841 or direct equivalent.
B -
SCR
4.2.10 RS232 CONNECTOR
NOTE:- RS232 connector is not fitted to the 7200 series controller.
PIN No
NOTES
1
Received Line Signal Detector (Data Carrier Detect)
2
Received Data
3
Transmit Data
4
Data Terminal Ready
5
Signal Ground
6
Data Set Ready
7
Request To Send
8
Clear To Send
9
Ring Indicator
View looking into the male connector on the 7000 series module
Location of RS232
connector
Location of RS485 connector