STOP mode is activated by pressing the
button.
In STOP mode, the module will remove the generator from load (if necessary) before stopping the engine if it is
already running.
If the engine does not stop when requested, the FAIL TO STOP alarm is activated (subject to the setting of the
Fail to Stop timer). To detect the engine at rest the following must occur :
•
Engine speed is zero as detected by the Magnetic Pickup or CANbus ECU (depending upon module
variant).
•
Generator frequency must be zero.
•
Oil pressure switch must be closed to indicate low oil pressure (MPU version only)
When the engine has stopped, it is possible to send configuration files to the module from DSE Configuration
Suite PC software and to enter the Front Panel Editor to change parameters.
Any latched alarms that have been cleared will be reset when STOP mode is entered.
The engine will not be started when in STOP mode. If remote start signals are given, the input is ignored until
AUTO mode is entered.
When configured to do so, if the generator has been on load, pressing the stop button will open the generator
breaker and force it to do a cooling run. If the stop button is activated again during the cooling run, the generator
will stop instantly.
When configured to do so, When left in STOP mode for five minutes with no presses of the fascia buttons, the
module enters low power mode. To ‘wake’ the module, press the
button or any other fascia control button.
Sleep mode configuration
in the DSE Configuration
Suite Software
Cool down in stop mode
configuration in the DSE
Configuration Suite Software