DSE7200 / 7300 Series Operators Manual
76
Transfer to generator
Operative in Manual Mode only
‘Normal’ breaker button control
•
Allows the operator to transfer the load to the generator
‘Alternative’ breaker button control (7320 V6+ only)
•
If mains is on load, transfers the load to the generator.
•
If generator is on load, opens the generator breaker
•
If generator and mains are off load, closes the generator breaker.
Open generator (DSE7210/DSE7310 only)
Allows the operator to open the generator (when in Manual mode only)
Transfer to mains
Operative in Manual Mode only
‘Normal’ breaker button control
•
Allows the operator to transfer the load to the mains
‘Alternative’ breaker button control (7320 V6+ only)
•
If generator is on load, transfers the load to the mains.
•
If mains is on load, opens the mains breaker
•
If generator and mains are off load, closes the mains breaker.
Menu navigation
Used for navigating the instrumentation, event log and configuration screens.
For further details, please see the more detailed description of these items elsewhere in this manual.