Important: Device Pairing Order
If a VT8000 controller that already has a SED-WIN & SED-DOR wireless switch paired with it is then
paired with an MPM, the paired wireless switch
will fail to function normally.
To avoid this problem,
always pair all VT8000 controllers to be used in a networked environment
with the appropriate MPMs before you pair them with SED-WIN & SED-DOR wireless switches.
As long as the sensors are paired with the controllers after the controllers are paired with the MPMs, the
switches will function normally. Only if the controllers are paired with the switches before they are paired
with the MPMs will the switches fail to function normally.
Before Starting Pairing Procedure
Verify that the following parameters on the VT8000 controller are set correctly to avoid failure in as-
sociating the wireless switch to the controller. For more information on the list of parameters, refer to the
VT8000 controller installation manual.
PAN ID
Personal Area Network
Identification
Default value = 0
Range: 0 -1000
This parameter will only appear when a wireless network
adapter is present. If the Terminal Equipment Controller
is installed as a stand-alone unit or with a BACnet™ or
Echelon™ adapter, this parameter will not be used or
displayed.
The default value of 0 is not a valid PAN ID.
The valid range of available PAN ID is from 1 to 1000.
Range 1 to 500 is for centralized networked applications using
a MPM with the wireless stat driver.
Range 501 to 1000 is for stand-alone applications where no
MPM with the wireless stat driver is used.
Channel
Channel selection
Default value = 10
Range: 11 - 25
This parameter will only appear when a wireless network
adapter is present. If the Terminal Equipment Controller
is installed as a stand-alone unit or with a BACnet™ or
Echelon™ adapter, this parameter will not be used or
displayed.
Schneider Electric recommends using only channels 15 and
25 only.
The default value of 10 is not a valid channel. The valid range
of available channel is from 11 to 25.