Pairing Process Procedure

NOTE: See VTR/VT installation manual for details on PAN ID parameter.

PAN ID for Centralized Networked Applications with MPM:

VT8000 Series

VT7000 Series

1 - 500

1 - 250

PAN ID for Stand-alone Applications with no MPM:

VT8000 Series

VT7000 Series

501 - 1000

N/A

Special note for all VT7000 Room Controllers: The VT7000 Room Controllers are only
compatible within a SmartStruxure network with MPM Controllers

Configuring Actions

Short Switch Duration

Result

Approx. 1 second

Enter Pairing Mode (page 8)

Approx. 1 second (after being paired)

Displays MAC address (page 8)

4+ seconds and less than 10 seconds

Battery Status (page 13 )

10+ seconds and less than 20 seconds

Diagnostic Mode (page 12)

20+ seconds

Resets Switch

Using VT8000 Controllers for Stand-alone Systems

When PAN ID is used with Range of 501 - 1000 for Stand-Alone Systems

In this application, the VT8000 controller(s) are the coordinators to their own systems and are
network masters for each wireless switch reporting to them. A unique network is needed for proper
functionality according to the following:

• Wireless controller factory default Channel and PAN ID = controller(s) offline.
• Each VT8000 controller is its own network coordinator.
• Range of PAN ID on all controllers to use is 501 - 1000. This range is reserved for stand-alone

system operation.

Notes:

• Each VT8000 Controller uses a unique PAN ID and/or Channel settings.
• If all available PAN ID’s are used (501-1000), use a different channel.
• Up to 20 switches can be linked to each VT8000 Controller.
• The MAC address is only used to confirm parent pairing.

Coordinator
VT8000 Series Controller
Channel: 15 PAN ID:

501

Coordinator
VT8000 Series Controller
Channel: 15 PAN ID:

502

Coordinator
VT8000 Series Controller
Channel: 15 PAN ID:

503

Window or Door Switch

Window or Door Switch

Window or Door Switch

Figure-6 Stand-alone VT8000 series systems