Viconics VZ7656F Wireless Installation Guide User Manual

Page 24

background image

24 | VZ7656F1000W Installation Guide

SH lock

Outside air temperature

supply heat lockout

Default value = 32 °F

(0 °C)

Disables heating operation based on outdoor air

temperature.

Please refer to the Viconics Zoning System Guide for

recommended settings.

From

–15 °F up to 120 °F (-26 °C up to 49 °C)

(increments: 5° or 50°)

C stage

VZ7656R1000B models only

Number of cooling stages

installed at RTU.

Default value = 2 stages

Will revert the operation of 2 stage controllers to a single

stage when the second cooling step is not needed.

1 or 2 stages

H lock
Outside air temperature
heating lockout
Default value = 120 °F (49
°C)

Disables heating stage operation based on outdoor air
temperature.
Function will only be enabled if OS ( outside air
temperature sensor ) is connected.
From -15 °F up to 120 °F (-26 °C up to 49 °C)

C lock
Outside air temperature
mechanical cooling lockout.
Default value = -40 °F(-40 °C)

Disables cooling stage operation based on outdoor air
temperature.
On economizer model, free cooling will not be disabled by
this function.
Function will only be enabled if OS (outside air
temperature sensor) is connected.
From -40 °F up to 95 °F ( -40 °C up to 35 °C )

2/4event
Number of events
configuration
Default value = 2 event

2 events, will set up scheduling for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
4 events, will set up scheduling for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
Event 3 is for Occupied setpoints
Event 4 is for Unoccupied setpoints