beautypg.com

Viconics VZ7656F Wireless Installation Guide User Manual

Page 20

background image

20 | VZ7656F1000W Installation Guide

Channel

Channel selection

Default value = 10

Range is: 10 to 26

This parameter (Channel) is used to link specific
controllers to specific Viconics wireless gateway(s) (VWG
/ Jace-Driver) or to the main VZ76xx RTU controller. For
any system, be sure you set the SAME channel value
both at the network coordinator and on all the VZ72xx
controller(s).

Viconics recommends using only the following channels:
15, 25 & 26.

The default value of 10 is NOT a valid channel. The valid
range of available channels range from 11 to 26.

Lockout Keypad lockout levels

Default value = 0 No lock

0 = No lock
1 = Low level
2 = High level

USER KEY FUNCTIONS

LEVEL

Global

Unocc.

Override

System mode

setting

Schedules

setting

Clock setting

0

1

2

pwr del

Power-up delay

Default value = 10 seconds

On initial power up of the Terminal Equipment Controller
(each time 24 VAC power supply is removed & re-applied)
there is a delay before any operation is authorized (fan,
cooling or heating). This can be used to sequence start up
multiple units / Terminal Equipment Controller in one
location.

10 to 120 seconds