Viconics VZ7656F Wireless Installation Guide User Manual
Page 22
22 | VZ7656F1000W Installation Guide
Min SH
Minimum supply heat
temperature setpoint
Default value = 64 °F
(18 °C)
Sets the minimum supply heat to be maintained by the
controller during occupied periods (Occupied or
Temporary Override).
50 °F to 72 °F (10 °C up to 22 °C)
(increments: 0.5° or 5°)
IMPORTANT: To be active, the Minimum Supply Air
Temperature control logic requires the following conditions
to be fulfilled:
-
Controller in Occupied mode
-
Controller in Heat mode
-
Outdoor Temperature < SH Lock setting
-
Discharge Air Temperature < Dis HL setting
Cool cph
Cooling stages cycles per
hour
Default value = 4 C.P.H.
Will set the maximum number of cooling stage cycles per
hour under normal control operation. It represents the
maximum number of cycles that the equipment will be
turned on and off in the span of an hour.
Note that a higher C.P.H will represent a higher accuracy
of control at the expense of wearing down mechanical
components faster.
3 or 4 C.P.H.
Deadband
Minimum deadband
Default value = 2.0 °F (1.1 °C)
Minimum deadband value between the heating and
cooling setpoints.
Used only with the setpoints used during communication
failure (ComLost Alarm) while operation is under the
return air sensor. If modified, it will be applied only when
any of the setpoints are modified.
2, 3 or 4 °F ( 1.0 to 2.0 °C )
Units
Sets the display scale of the
controller
Default value = Imp
0 = SI for Celsius / Pa pressure scale.
1 = Imp for Fahrenheit / in. WC pressure scale.
fan del
Fan delay
Default value = Off
Fan delay extends fan operation by 60 seconds after the
call for heating or cooling ends.
Valid only for Auto
fan mode. “On” fan mode will leave the
fan always on.
Off or On