22 | VZ7656F1000W Installation Guide

Min SH

Minimum supply heat

temperature setpoint

Default value = 64 °F

(18 °C)

Sets the minimum supply heat to be maintained by the

controller during occupied periods (Occupied or

Temporary Override).

50 °F to 72 °F (10 °C up to 22 °C)

(increments: 0.5° or 5°)

IMPORTANT: To be active, the Minimum Supply Air

Temperature control logic requires the following conditions

to be fulfilled:

-

Controller in Occupied mode

-

Controller in Heat mode

-

Outdoor Temperature < SH Lock setting

-

Discharge Air Temperature < Dis HL setting

Cool cph

Cooling stages cycles per

hour

Default value = 4 C.P.H.

Will set the maximum number of cooling stage cycles per

hour under normal control operation. It represents the

maximum number of cycles that the equipment will be

turned on and off in the span of an hour.

Note that a higher C.P.H will represent a higher accuracy

of control at the expense of wearing down mechanical

components faster.

3 or 4 C.P.H.

Deadband

Minimum deadband

Default value = 2.0 °F (1.1 °C)

Minimum deadband value between the heating and

cooling setpoints.

Used only with the setpoints used during communication

failure (ComLost Alarm) while operation is under the

return air sensor. If modified, it will be applied only when

any of the setpoints are modified.

2, 3 or 4 °F ( 1.0 to 2.0 °C )

Units
Sets the display scale of the
controller

Default value = Imp

0 = SI for Celsius / Pa pressure scale.

1 = Imp for Fahrenheit / in. WC pressure scale.

fan del
Fan delay
Default value = Off

Fan delay extends fan operation by 60 seconds after the
call for heating or cooling ends.
Valid only for Auto

fan mode. “On” fan mode will leave the

fan always on.
Off or On