beautypg.com

Viconics VTR7300 Application Manual User Manual

Page 5

background image

5

Typical line wiring one to one setup

Line Voltage Electrical Ratings

VC3500E5000

VC3504E5000

VC3400E5000

VC3404E5000

VC3300E5000

Slave Fan Unit

Power supply

-

90 to 277 Vac universal all models

-

Black Hot L1 Power Vac ( Switches: Brown, Blue, Red & Yellow )

-

White Neutral Power Vac

Fan line voltage contact

Wire connections

½ HP Maximum

3 Fan Speed
Control Wires

Brown, Blue, Red

3 Fan Speed
Control Wires

Brown, Blue, Red

3 Fan Speed
Control Wires

Brown, Blue, Red

3 Fan Speed
Control Wires

Brown, Blue, Red

3 Fan Speed
Control Wires

Brown, Blue, Red

Valve line voltage
contact

Yellow wire connection

10A maximum

4 Pipes Cool output

Or

2 Pipes Heat / Cool
output

4 Pipes Cool output

Or

2 Pipes Heat / Cool
output

2 Pipes Heat / Cool
output

2 Pipes Heat / Cool
output

N/A

Valve line voltage
contact

Orange wire
connections

10A maximum

4 Pipes Heat output

Isolated dry contact
output

Or

2 Pipes reheat
output

4 Pipes Heat output

Isolated dry contact
output

Or

2 Pipes reheat
output

N/A N/A N/A

VC3504E

Relay Pack

Black - Hot Power
Orange - Connected to Black Hot
White - Neutral

Brown - High Speed
Blue - Medium Speed
Red - Low Speed

M

3 Speed

Applications

2 Speed

Applications

Single Speed

Applications

For 2 pipe applications use cooling valve yellow wire connection

Fan Speed Arrangement
By Configuration

M

Orange - Heating Valve

Yellow - Cooling Valve

V

V

M

Orange - Electric Reheat

R

For electric reheat applications where current draw is under above 10 A
use a line powered coil pilot duty relay or contactor for the heating element
in place of the heating valve