Viconics VTR7300 Application Manual User Manual

Page 24

background image

24

C or F
Sets scale of the Terminal
Equipment Controller
Default value = °F

°F for Fahrenheit scale
°C for Celsius scale
On hotel models, this sets the default value when the Terminal Equipment
Controller powers up

%RH disp
Local %RH Display

Default value = OFF
Models with Humidity sensor only

Conditional parameter to Humidity models VTR735xX5x00(X)
Enables the display of humidity below the room temperature on the display

ON
= Display %RH
OFF = No display of %RH

Lockout
Keypad lockout levels
Default value = 0 No lock

Level

Occupied temperature

setpoints

System mode setting

Fan mode setting

Unoccupied Override

0

Yes access

Yes access

Yes access

Yes access

1 Yes

access

Yes access

Yes access

No access

2

Yes access

No access

No access

Yes access

3

Yes access

No access

No access

No access

4

No access

No access

No access

Yes access

5

No access

No access

No access

No access

PulsedHt
Enable pulsed electric heat
Default Value = Off

Enables Vdc modulating pulsed electric reheat applications used with SSR’s.
Only used with VC340xX Relay Pack models

Off
= Regular On-Off control for VR7300A & C models
Can be used with 2 pipes & 4 pipes applications
On = 10 second pulsed time base modulation for VR7300B & E models
Can only be used with 2 pipes
The VR7300B & E cannot be used for 4 pipes applications

Pipe No

System type installation
Number of pipes
Default is: 4.0 Pipes

Defines the type of system installed

2.0 Pipes, will limit the number of sequences of operation available from 0 to 2
Will enable heat/cool operation from the same output

4.0 Pipes, can access all the sequences of operation from 0 to 4
Will enable heat/cool operation from different output

SeqOpera Sequence of operation
Default is: Sequence #1

Selects the initial sequence of operation required by the installation type and the
application

System = 2 Pipes

VR7300A, B C & E Models

System = 4 Pipes

VR7300A & C Models only

0 = Cooling Only

Yes access

Yes access

1 = Heating Only

Yes access

Yes access

2 =
Cooling / Heating
Cooling With Electric Reheat

Yes access

Cooling With Electric Reheat

Yes access

Cooling / Heating

3 = Heating With Electric Reheat

Yes access

No access

4 = Electric Reheat Only

Yes access

No access

For 2 Pipe output applications, the system access is also limited if RUI 1 is
configured for local changeover COS, COC/NC or COC/NC. The current water
temperature detected by the RUI 1 then limits the system mode available for the
local configuration or network write.

For sequence 2 & 3, set PulsedHt to On to enable pulsed electric reheat
applications with VR7300B & E

Fan Menu
Mode button menu configuration
Default is: Menu #4

Menu presented are dependent on model used and sequence of operation
selected
Auto Mode operation for sequences 2 and 3 is dependent on Auto Fan parameter

0 = Low-Med-High

3 Speed configuration using 3 fan relays ( L-M-H )

1 = Low-High

2 Speed configuration using 2 fan relays ( L-H )

2 = Low-Med-High-Auto

3 Speed configuration with Auto fan speed mode using 3 fan relays ( L-M-H )

3 = Low-High-Auto

2 Speed configuration with Auto fan speed mode using 2 fan relays ( L-H )

4 = On-Auto

Single Speed configuration. Auto is for Fan on demand / On is On all the time