Page 25

background image

25

DHumiLCK
Dehumidification lockout

Default value: On = Authorized

Conditional parameter to Humidity models VTR735xX5x00(X)
Typically toggled through the network.
This variable enables or disables dehumidification based on central network
requirements from the BAS front end
On = Dehumidification Authorized
Off = Dehumidification Not Authorized

%RH set
Dehumidification setpoint
Default is 50 % RH

Conditional parameter to Humidity models VTR735xX5x00(X)
Used only if dehumidification sequence is enabled:
Range is: 30-95% RH

DehuHyst
Dehumidification Hysterisys
Default is 5 % RH

Conditional parameter to Humidity models VTR735xX5x00(X)
Humidity control hysterisys. Used only if dehumidification sequence is enabled:
Range is: 2 to 20% RH

DehuCool
Maximum Dehumidification
Cooling output
Default is 100 %

Conditional parameter to Humidity models VTR735xX5x00(X)
Maximum cooling valve position when dehumidification is enabled. This can be
used to balance smaller reheat loads installed in regards to the capacity of the
cooling coil.
Range is: 20 to 100 %

St-By TM
Stand-by Timer value
Default 0.5 hours

Time delay between the moment where the PIR cover detected the last movement
in the area and the time which the Terminal Equipment Controller stand-by mode
and setpoints become active.
Range is: 0.5 to 24.0 hours in 0.5hr increments

Unocc TM
Unoccupied Timer value
Default 0.0 hours

Time delay between the moment where the Terminal Equipment Controller toggles
to stand-by mode and the time which the Terminal Equipment Controller
unoccupied mode and setpoints become active.
The factory value or 0.0 hours: Setting this parameter to its default value of 0.0
hours disables the unoccupied timer. This prevents the Terminal Equipment
Controller to drift from stand-by mode to unoccupied mode when PIR functions are
used
Range is: 0.0 to 24.0 hours in 0.5hr increments

St-By HT
Stand-by heating setpoint
Default value = 69 °F

The value of this parameter should reside between the occupied and unoccupied
heating setpoints and make sure that the difference between the stand-by and
occupied value can be recovered in a timely fashion when movement is detected
in the zone.
Stand-by heating setpoint range is: 40 to 90 °F ( 4.5 to 32.0 °C )

St-By CL
Stand-by cooling setpoint limit
Default value = 78 °F

The value of this parameter should reside between the occupied and unoccupied
cooling setpoints and make sure that the difference between the stand-by and
occupied value can be recovered in a timely fashion when movement is detected
in the zone.
Stand-by cooling setpoint range is: 54 to 100 °F ( 12.0 to 37.5 °C )

Unocc HT
Unoccupied heating setpoint
Default value = 62 °F

Unoccupied heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )

Unocc CL
Unoccupied cooling setpoint limit
Default value = 80 °F

Unoccupied cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )

heat max
Maximum heating setpoint limit
Default value = 90 °F ( 32 °C )

Maximum occupied & unoccupied heating setpoint adjustment.
Heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )

cool min
Minimum cooling setpoint limit
Default value = 54 °F ( 12 °C )

Minimum occupied & unoccupied cooling setpoint adjustment.
Cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )