Viconics VTR7300 Application Manual User Manual
Page 4
4
VTR73xxA Occupancy function remote inputs. All wiring for those remote inputs is located at the wall VTR73xxA
Terminal Equipment Controller.
o
BI1 can be configured for:
None = no functions associated
Motion NO = for a remote normally opened contact PIR motion sensor
Motion NC = for a remote normally closed contact PIR motion sensor
Rem NSB = for usage with a remote on-off contact device for the occupancy function. A typical application
is a room tenant card holder, which force the occupancy if the card is inserted in the holder.
Window = A local and / or networked window opened alarm. The system heating and cooling actions are
also locked out.
o
BI2 can be configured for:
None = no functions associated
DoorDry = for usage of a PIR and entrance door switch for lodging occupancy routine
All communication wires ( if needed ) are located at the VTR73xxA Terminal Equipment Controller
Typical one to one set-up
Existing or New Field VTR7300 Wires
3 minimum required 14-22 Ga
Solid or Stranded
H
C
High Voltage in cabinet wiring
- Line powered 90 to 277 Vac
- Line switching of fan & valves 90 to 277 Vac
- Isolated heating output for electric reheat
Line Voltage Power
Line Voltage Valves
- 2 pipes or 4 pipes applications
- Isolated line switching for electric reheat
Line Voltage Fan
- Configurable
- Up to 3 speed
fan control
- Auto fan speed
Local Inputs at VTR7300 Controller
Special optional local function(s):
- Remote motion detector(s)
- Window contacts
- Occupancy card holder
Model Dependent
Optional FCU Monitoring Inputs
- Service or Filter alarms
- Supply air sensor
- Return air sensor
- Changeover sensor or contact
Existing or New Communication Field Wires
- BACnet MS-TP
- LON TP-FT 10
- Wireless ( No wires )