Notice – VACUUBRAND PC 301 User Manual
Page 22
Documents are only to be used and distributed completely and unchanged. It is strictly the users´ responsibility to check carefully
the validity of this document with respect to his product. Manual-no.: 999147 / 17/06/2014
page 22 of 40
In case of overload, the motor is shut down by a
self-hold thermal circuit breaker
in the winding.
Note: Only a manual reset is possible. Switch off the pump and disconnect the elec-
trical power cord. Identify and eliminate the cause of failure. Wait approximately five
minutes before restarting the pump.
•
Note: In case of supply voltage below 100V, the lock of the breaker may not
latch and the pump might restart on its own after sufficient cooling. Take appro-
priate precautions, if an automatic restart of the pump may lead to a dangerous
situation.
A warm up period (approximately 15 min.) is required to ensure that the rated ulti-
mate vacuum and pumping speed are attained. Avoid overheating (e.g., due to hot
process gases).
Attention: Important notes regarding the use of gas ballast
➨
Air and pumped media might react inside the pump or at the outlet of the pump
and form hazardous or explosive mixtures, when you use air rather than inert gas
for the gas ballast. This constitutes a risk of significant damage to equipment and/
or facilities, a risk of personal injury or even loss of life.
☞
Make sure that air/gas intake through the gas ballast valve can never lead to
hazardous, explosive or otherwise dangerous mixtures. If in doubt, use inert gas.
For
condensable vapours (water vapour, solvents, ...):
- Do not pump condensable vapours before the pump has
reached its operating temperature. Do not pump conden-
sable vapours with a closed gas ballast valve.
- Open gas ballast valve. Start pumping vapours only once
the pump has reached its operating temperature.
- The gas ballast valve is open, if the arrow on the gas bal-
last cap points towards the pump.
- With gas ballast valve open, the ultimate vacuum will be
reduced.
- Use inert gas for gas ballast to avoid the formation of ex-
plosive mixtures.
Attention: maximum supply pressure of
inert gas: 1.2 bar absolute.
- Close the gas ballast valve by turning the cap 180°.
In case of low boiling solvents (when the formation of condensate is unlikely), the
use of gas ballast might be unnecessary.
In case of
condensation: Check the liquid level in both catchpots during opera-
tion. Check the liquid level in both catchpots regularly. Do not allow the catchpots to
overfill. Drain catchpots in time to avoid overflow. Install a level sensor (see „Acces-
sories“) for monitoring, if necessary (VACUUBRAND controller CVC 3000 or VNC 2
is required).
The maximum liquid level is at approximately 80% of the total filling level to avoid
problems when removing the catchpots.
Removing the catchpots:
Catchpot at outlet:
Remove joint clip. Remove catchpot and drain condensate.
gas
ballast
NOTICE