Thermostatic 2-Pipe Total Electric Heat with-
Valve Control —

With this system, the complete heat-

ing requirement for the space is provided by the electric heater;
the water system is never changed over for heating. It is there-
fore possible, just as with 4-pipe systems, to have heating or
cooling at any time of the year.

The fan runs continuously unless it is manually switched

to OFF position. Fan must be on before thermostat can send
signal to open chilled water valve or turn on electric heater.

Normally, an automatic changeover thermostat with a dead

band between heating and cooling is used, but a manual

changeover thermostat is also suitable. A 2-way or 3-way
valve must also be used so that the chilled water is off when-
ever the heater is on. No changeover device to sense water
temperature is necessary.
NOTE: Wiring diagrams are for 120-v power supply. If other
voltages for heaters or controls are specified, wiring may dif-
fer from that shown.

For control package descriptions, see control components

sections entitled Remote-Mounted Controls and Unit-
Mounted Controls.

UNIT

TYPE

LOCATION

WIRING PACKAGE*

ELECTRIC

VALVE

Automatic System

Manual System

Vertical

Unit

Mounted

24-Q

Available on Special Order.

Any 2- or 3-way,

2-position valve

Package.

Vertical

or

Horizontal

Wall Mounted

22-J, 22-K,

23-09, 23-10

23-15, 23-16

*Packages on current price pages.

NOTES:
1. Motors thermally protected.
2. Use copper conductors only.
3. See unit nameplate for power supply. Provide disconnect means

and overload protection as required.

7