beautypg.com

Carrier 42 SERIES User Manual

Page 25

background image

SYMBOL/SKETCH

DESCRIPTION

CV FACTOR

RATING

STEAM

USE

1

2

3

4

PSI

F

PRESSURE TEST PORT: Brass body

1

4

service access fitting with

removable depressor type core.

Application - Installed on both sides of
the coil to allow for pressure sensing.
Attach pressure gages to facilitate
close tolerance water balancing.

N/A

N/A

400

210

NO

GAGE COCK: Brass shut-off valve
with

1

4

FPT fitting for attachment of

pressure gages.

Application - Installed on both sides of
the coil to allow for pressure sensing.
Attach pressure gages to facilitate
close tolerance water balancing. May
be used in bleed bypass line to
regulate water flow.

N/A

N/A

200

250

N/A

B + G

CIRCUIT SETTER: Variable water
flow balancing valve with manual
adjustment knob, pointer, percent-open
scale, memory stop and integral
pressure read-out ports.

Application - Used for close tolerance
water flow balancing. Positive shut-off
ball valve feature allows usage as com-
bination balancing and shut-off valve.

1.95

4.15

200

250

NO

BALANCE VALVE: Variable water
flow manual balancing valve with
screwdriver slot adjustment screw.

Application - Often used in conjunction
with test port fittings for water flow
balancing. Balance by temperature
differential or coil pressure drop (check
specifications for service fittings
required if balancing by pressure drop).
May be used in 3-way valve bypass
line to permit equal flow balancing.

3.0

8.9

150

200

NO

FLOW SETTER: Variable water flow
manual balancing valve with
screwdriver slot adjustment and direct
gpm read-out sight glass.

Application - Used for water flow
balancing (8.0 gpm maximum).

2.2

5.4

125

210

NO

FIXED FLOW VALVE: Spring and
insert type (non-adjustable).

Application - Used for water flow
balancing. Valve automatically adjusts
the flow to within 10% of set point. Not
available for flow rates above 8 gpm.

Valve orifice size
determines CV

factor. The orifice
of these fixed flow
valves changes as
flow is regulated.
As the water
pressure increases,
the orifice size
decreases, thereby
automatically
limiting the flow
rate to the
specified gpm
(+/

Ϫ

10%).

125

240

NO

HAYES

FIXED FLOW VALVE: Flexible orifice
type (non-adjustable).

Application - Used for water flow
balancing. Valve automatically adjusts
the flow to within 10% of set point.
Requires 15 psi (35 ft) of additional
pump head for proper operation.

150

160

NO

25