REMOTE-MOUNTED CONTROLS

Standard 3-Speed Switch —

This standard switch

has 4 positions: OFF, HIGH, MEDIUM, and LOW. Switch
has auxiliary contact that is energized when switch is in HIGH,
MEDIUM or LOW position.
Some of the options common with the 3-speed switch are:
1. Unit-mounted switch on Furred-In Vertical Model. (Avail-

able as special order on Horizontal Models)

2. Switch without OFF position.
3. Key-operated switch.

Combination

Thermostat/3-Speed

Switch

(Packages 22-B, 22-D, 22-F, 22-H, 22-K*) — Thermostat
and standard switch are mounted on a common decorative
wall plate, suitable for installation in a 4

11

16

-in. square junc-

tion box. Packages 22-A and 22-B include Model TC-126
2-pipe heating and cooling thermostat and automatic change-
over switch (shipped separately for field wiring and mount-
ing).

Packages 22-C and 22-D include Model TC-126 thermo-

stat less automatic changeover switch wired for cooling only.

Packages 22-E and 22-F include Model TC-126 thermo-

stat, less automatic changeover, wired for heating only.

Package 22-G includes Model TH-126 4-pipe thermostat

for sequenced heating and cooling, plus 3-speed switch. (For
4-pipe or total electric heat systems.)

Package 22-J is the same as 22-G except that 2 automatic

changeover switches are shipped with package. (For auxil-
iary electric heat systems.)

Wall Thermostat, 2-Pipe

(Packages 22-A through

22-F*) — Model TC-126 thermostat for heating and cool-
ing, operates on line voltage. Action is SPDT. Temperature
range is 50-90 F.

Packages 22-A and 22-B — Heating and cooling, in-

cludes one automatic changeover switch (shipped separately
for field wiring and mounting).

Wall Thermostat, 4-Pipe

(Packages 22-G through

22-K*) — Model TH-126 thermostat is also used on 2-pipe
system with electric heat. Heating and cooling are se-
quenced (automatic changeover) with 6 degree separation be-
tween HEATING ON and COOLING ON. Temperature range
is 50 - 90 F.

Packages 22-G and 22-H — For 4-pipe and total electric

heat systems.

Packages 22-J and 22-K — For auxiliary electric heat sys-

tems, includes 2 automatic changeover switches (shipped sepa-
rately for field wiring and mounting).

* Packages listed on current price pages.

50

60

70

80

90

50

60

70

80

90

Thermostat Electrical Data

(Pilot Duty — 125 VA)

VOLTS

HEATING

COOLING

FLA

LRA

FLA

LRA

120

5.8

34.8

5.8

34.8

240

4.9

29.4

4.9

29.4

277

4.1

24.6

4.1

24.6