VHS Models

11

Table 1. Masonry Vitreous Tile-Lined Chimney (not metal lined)

Chimneys not exposed to the outdoors below the roof line. (5" dia. vent adapter must be used)

Natural Draft Chimney and Type “B” Venting Tables

Additional

National Fuel Gas Code

Boiler

Gas Appliance

Reference Table No.*

Model(s) †

in Venting System

Connector

Requirements*

(ANSI Z223.1)

VHS-90

No

Type “B”

1. Connector diameter must be upsized to 7".

VHS-120

2. Chimney height limits: Min. 15 ft., Max. 30 ft.

VHS-150

3. Lateral length restriction applies (Table 13.1 (c))

13.1 (c) (2006 edition)

VHS-180

4. Internal area of chimney: Min. 50 sq. in.,

Max. 269 sq. in.

VHS-180

No

Single-wall

1. Connector diameter must be upsized to 7".
2. Chimney height limits: Min. 15 ft., Max. 30 ft.
3. Max. lateral length may not exceed 2 ft.

13.1 (d) (2006 edition)

4. Internal area of chimney: Min. 50 sq. in.,

Max. 269 sq. in.

VHS-90

Yes

Type “B”

1. See Table 13.2 (c) for chimney height

VHS-120

and connector length restrictions.

13.2 (c) (2006 edition)

VHS-150

2. Connector may have to be upsized to 6" diameter

VHS-180

to meet requirement of 10-8.

VHS-150

Yes

Single-wall

1. See Table 13.2 (d) for chimney height

VHS-180

and connector length restrictions.

13.2 (d) (2006 edition)

2. Connector may have to be upsized to 6" diameter

to meet requirement of 13.2 (d).

Additional

National Fuel Gas Code

Boiler

Gas Appliance

Reference Table No.*

Model(s) †

in Venting System

Connector

Requirements*

(ANSI Z223.1)

VHS-90

No

Type “B”

See Table 13.1 (a) for minimum and maximum

VHS-120

of vent height and lateral length restriction.

VHS-150

13.1 (a) (2006 edition)

VHS-180

VHS-90

No

Single-wall

See Table 13.1 (b) for minimum and maximum

VHS-120

of vent height and lateral length restriction.

VHS-150

13.1 (b) (2006 edition)

VHS-180

VHS-90

Yes

Type “B”

1. See Table 13.2 (a) for vent height and

VHS-120

connector length restrictions.

VHS-150

2. Connector and vent diameter may have to be

13.2 (a) (2006 edition)

VHS-180

increased to 6" or 7" to meet requirement of
Table 13.2 (a).

VHS-120

Yes

Single-wall

1. See Table 13.2 (b) for vent height and

VHS-150

connector length restrictions.

VHS-180

2. Connector and vent diameter may have to be

13.2 (b) (2006 edition)

increased to 6" to meet requirement of
Table 13.2 (b).

Table 2. Type “B” Venting and Metal-Lined Masonry Chimney

UL LISTED MATERIALS ONLY. (5" dia. vent adapter must be used)

† Only Victory

II

boiler models shown for each application permitted to be installed in that manner specified.

• Also see ANSI Z223.1 –– 2006 Chapter 12 and 13.