VisorALARM PLUS 2U Operating

III - 7

Doc.DM375-I

Ver.1.0

2. Operating in manual mode

When the VisorALARM PLUS 2U receiver has no Automation Software connected or the Automation
Software has failed, the receiver must be operated in manual mode.

In manual mode signals must be visualized and acknowledged from the receiver through the receiver
LCD and keypad.

When a signal arrives at the receiver in manual mode, the LCD shows a status line as follows:

If you are not logged into the VisorALARM PLUS 2U receiver when events are received pressing the
ACK key for the first time will display the highest priority event and silence the receiver piezo. If the
ACK key is pressed a second time you will be prompted for a password. Upon entering the password
the event with the highest priority is resounded. Repeatedly pressing the ACK key will now display
and acknowledge subsequent events.

Subsequently the signal information is shown in the display with the next format:

The LCD shows the following information:

§ hh:mm:ss: The hour, minutes and seconds of the alarm in a 24 hours format
§ aaaaaaaa: The eight digit account code
§ Q: Qualificator, E= New event or opening; R=Restoration or closing; P=Status report.
§ XYZ: Event code
§ GG: Number or group or partition.
§ CCC: Zone number or user identifier.
§ TTTTTTT: Textual description for the event code. This contemplates the following values:

Event Code

TTTTTTT

10x

Medical

11x

Fire

12x

Panic

13x

Burglar

14x, …, 1Fx

Alarm

2xx

Superv

3xx

Trouble

4xx

Opn/Cls

hh:mm:ss aaaaaaaa »
QXYZ GG CCC TTTTTTTTT

16:33:23 00001234 »
E110 01 001 Fire

PRIMARY VisorALARM

1 Signal pending