DIP Switch Settings
Program Options via DIP Switch
3.1 DIP Switch Settings
The following tables list the programmable features for the SK-2 and SK-4. Placing a DIP switch
in the ON position will select the feature while placing the DIP switch in the OFF position will
deselect the feature. The exceptions to this rule are SW3 DIP switches 5 & 6. These two switches
are used to select the Notification Appliance Circuit synchronization feature. A detailed description
of each feature is presented in the following pages.
Important: When any programmable feature is changed by repositioning a DIP switch, the FACP
Reset button must be pressed to ensure that the control panel can read the new switch position.
Switch Number
DIP Switch Number
DIP Switch ON
SW1
1
Silence Inhibit
2
Auto-silence
3
Temporal Coding
4
Selective Silence (if sync. enabled)
5
Trouble Reminder
6
AC Trouble Delay
7
Autoresettable Supervisory
8
IDC Combination
Waterflow/Supervisory Circuit
SW2
1
not used
2
not used
3
IDC1 Verification
4
IDC1 Supervisory
5
IDC2 Verification
6
IDC2 Supervisory
7
not used
8
not used
SW3
1
NAC1 Nonsilenceable
2
NAC1 Disable
3
not used
4
not used
5 & 6
used to select strobe
synchronization feature as
shown to the right
Switch 5
Switch 6
No Synchronization
OFF
OFF
System Sensor Synchronization
ON
OFF
Gentex Synchronization
OFF
ON
Wheelock Synchronization
ON
ON
7
Nonsilenceable Waterflow for
Combination Circuit
(only if SW1 switch 8 is ON)
8
spare
Table 3.1 SK-2 DIP Switch Settings