2 special application dc power output connections, 3 relays – SilentKnight SK-4 Conventional FACP 2 & 4 Zone User Manual
Page 23
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
23
Output Circuits
Installation
2.4.2 Special Application DC Power Output Connections
Resettable 24 VDC special application power is available on both the SK-2 and SK-4 control
panels. Nonresettable 24 VDC special application power is available only on the SK-4.
2.4.3 Relays
The SK-2 and SK-4 control panels provide an alarm and fail-safe trouble relay and the SK-4 also
provides a supervisory relay. Each Form-C relay is rated for 2 amps @ 30VAC (resistive).
Note that relay connections may be power-limited or nonpower-limited, provided that 0.25”
minimum spacing is maintained between conductors of power-limited and nonpower-limited
circuits.
TB1
Figure 2.7 Special Application Power
4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, resettable special application power for
4-wire smoke detectors can be obtained from these
terminals (power-limited)
Nonresettable Power (500 mA) -SK-4Only
24 VDC filtered, nonresettable special application power
can be obtained from
these terminals (power-limited)
+ - + -
ms-
4t
b
1.
wmf
TB
5
TB
6
TB
7
TROUBLE
C TRBL NORM
C NC NO
ALARM
SUPV
C NC NO
Figure 2.8 Relay Terminals
Note: Relay contacts are shown with
power applied to the panel and no active
troubles, alarms or supervisories.
The Trouble Relay is a fail-safe relay
which will transfer on any trouble or total
power failure.
m
s4r
el
ay.
w
m
f