beautypg.com

2 special application dc power output connections, 3 relays – SilentKnight SK-4 Conventional FACP 2 & 4 Zone User Manual

Page 23

background image

SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010

23

Output Circuits

Installation

2.4.2 Special Application DC Power Output Connections

Resettable 24 VDC special application power is available on both the SK-2 and SK-4 control
panels. Nonresettable 24 VDC special application power is available only on the SK-4.

2.4.3 Relays

The SK-2 and SK-4 control panels provide an alarm and fail-safe trouble relay and the SK-4 also
provides a supervisory relay. Each Form-C relay is rated for 2 amps @ 30VAC (resistive).

Note that relay connections may be power-limited or nonpower-limited, provided that 0.25”
minimum spacing is maintained between conductors of power-limited and nonpower-limited
circuits.

TB1

Figure 2.7 Special Application Power

4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, resettable special application power for
4-wire smoke detectors can be obtained from these
terminals (power-limited)

Nonresettable Power (500 mA) -SK-4Only
24 VDC filtered, nonresettable special application power
can be obtained from
these terminals (power-limited)

+ - + -

ms-

4t

b

1.

wmf

TB
5

TB
6

TB
7

TROUBLE

C TRBL NORM

C NC NO

ALARM

SUPV

C NC NO

Figure 2.8 Relay Terminals

Note: Relay contacts are shown with
power applied to the panel and no active
troubles, alarms or supervisories.
The Trouble Relay is a fail-safe relay
which will transfer on any trouble or total
power failure.

m

s4r

el

ay.

w

m

f

This manual is related to the following products: