SYS TEM CHECK

1.

Disconnect main power to unit.

2.

Install jumper on auxiliary contacts of blower contactor in

main unit control box.

3.

Turn thermostat control to “OFF” position.

4.

Install jumper on damper motor terminals T and T1. See

Figure 9.

5.

Restore power to unit. Damper should drive to fully opened

position (requires 1 ½ minutes for full travel). Observe travel

for proper damper operation.

6.

Disconnect power to unit. Damper should spring return to

closed position.

7.

Remove T and T1 jumper on damper motor, then restore

power to unit. Adjust minimum vent position on potentiometer

on damper motor. See Figure 10.

8.

Disconnect power to unit and remove jumper on auxiliary

contacts of blower contactor in main unit control box. Restore

power to unit.

MAIN TE NANCE

1.

Damper motor is prelubricated and does not require further

lubrication.

2.

Make visual inspection of dampers and linkage assemblies

during routine maintenance.

3.

Filters should be checked periodically and cleaned when

necessary.

4.

The washable filters supplied with the economizer can be

cleaned with water and a mild detergent.

5.

Take note of “Air Flow Direction” marking on filter frame when

reinstalling.

6.

If filter must be replaced, filter of like kind and size must be

used. DO NOT replace permanent filters with throwaway

type filters.