beautypg.com

Installation instruction, Down flow application, Horizontal application – Reznor R6GP Option - Installation - Economizer - Lt Commercial User Manual

Page 2

background image

TB11 BOARD AND LOGIC CON TROL

FIL TERS

INTAKE AIR

EXHAUST AIR

Figure 3

DAMPER MOTOR

ENTHALPY SENSOR

S1 UNIT JACK

MIXED AIR SENSOR

DOWN FLOW APPLICATION

Figure 4

FILTER ACCESS

SCREW TO SIDE MULLIONS

FRESH AIR HOOD

BAROMETRIC

RELIEF HOOD

12. Install barometric relief hood in front

of exhaust air opening.

13. Install fresh air hood in front of intake

opening.

14. Slide filter access panel underneath

top of unit and secure to mullions.

a.

For heatpump units refer to

Section IV before restoring the
unit power.

15. Restore power to unit and check for

proper damper operation (See
System Check section).

12. Install barometric relief hood to

return duct over the opening in
duct.

13. Install fresh air hood in front of

intake opening.

1 4 . S l i d e f il t e r a c c e s s p a n e l

underneath top of unit and
secure to mullions.

a.

For heatpump units refer to
Section IV before restoring
the unit power.

15. Restore power to unit and check

for proper damper operation
(See System Check section).

BAROMETRIC RELIEF HOOD

FRESH AIR HOOD

Figure 5

8.

Position logic control board in filter access area as
shown in Figure 3. Secure control board with two
#10-16 x ½ screws.

9.

Insert mixed air sensor tube through the mounting
hole into the supply air compartment. Secure using
two #10-16 x ½ screws. See Figure 3.

10. Connect economizer plug P1 to unit jack S1 on units

economizer control panel.

11. Verify that wire harnesses are secure and will not

interfere with economizer vane and linkage
operation, or with a filter change out

Note: Leave unit dummy plug (from Step 5) in the

unit control panel for later use if the
economizer needs to be by passed.

FILTER ACCESS

INSTALLATION

INSTRUCTION

INSTALLATION INSTRUCTIONS FOR

559374

ECONOMIZERS USED WITH Q5SN / Q6SP 090-120

P6 / R6 120 UNITS

NOTE:

FOR THIS APPLICATION, HORIZONTAL
DUCT KIT #547881 IS REQUIRED.

HORIZONTAL APPLICATION

2

CUT HOLE

559374 - 31" x 18

3

8

SUPPLY DUCT

30 x 16

3

8

RETURN DUCT

31 x 18 ¾

This manual is related to the following products: