Caution, Warning – Reznor R6GN Option - Installation - LP Conv Kit User Manual
Page 4

4
EXAMPLE 2:
•	 For	a	high	fire	flow	rate	of	68	cu.	ft.	gas	per	hour.
•	 Local	heating	value	of	LP	gas	(obtained	from	gas	
supplier) = 2,500 Btu per cu. ft.
• Input rate = 2,500 x 68 = 170,000 Btuh.
LIGHTING & ADjUsTMENT OF
THE APPLIANCE
1. Turn ON the gas at the manual valve, outside of the unit.
2. Check all gas connections for leaks with a soap and water 
solution. If the solution bubbles, there is a gas leak which 
must be corrected. 
DO NOT use an open flame to check
for gas leaks.
3. Turn ON the electrical power to the appliance.
4. Move the gas valve lever/switch/knob to the ON position. See 
Figure 2 (page 5). NOTE: The lever/knob must be moved to 
the end of its range of motion to insure the valve is completely 
open. Use only your hand to push in or turn the gas control 
valve. Never use tools.
5. Set the room thermostat to a point above room temperature
to begin the heating cycle of the unit.
6. Check that the unit ignites and operates properly. Refer to the
installation instructions provided with your unit for the normal 
operating sequence.
7. After the flame ignites, visually inspect the burner assembly
to ensure that the flame is drawn directly into the center of the 
heat exchanger tube. The end of the flame will be out of sight 
around the bend of the heat exchanger tube. In a properly 
adjusted burner assembly, the flame color should be blue 
with some light yellow streaks near the outer portions of the 
flame.
NOTE: Until all of the air is bled out of the gas line, the spark 
ignitor may not ignite the gas. If the ignition control locks out, turn 
the thermostat to its lowest setting and wait one minute then turn 
the thermostat to a point above room temperature. The ignitor 
will try again to ignite the main burners. This process may have 
to be repeated several times before the burners will ignite. After 
the burners are lit, check all gas connections for leaks again with 
the soap and water solution. If the solution bubbles, there is a 
gas leak which must be corrected. Do not use an open flame 
to check for gas leaks.
VERIFYING & ADjUsTING FIRING RATE
The input firing rate must be verified for each installation to 
prevent over-firing of the unit.
CAUTION:
Do not re-drill the burner orifices. If the orifice size
must be changed, use only new orifices.
ImPORTANT	NOTe:	The	firing	rate	must	not	exceed	the	rate	
shown	on	the	unit	data	label.	At	altitudes	above	2,000	ft.,	it	
must	not	exceed	that	on	the	data	label	less	4%	for	each	1,000	
ft.	Follow	the	steps	below	to	determine	the	unit	firing	rate:
• For installations at 2,000 feet and less, the firing rate
is the same as shown on the unit rating label.
• For installations above 2,000 feet, calculate the correct
firing rate as shown in Example 1.
• Table 2 (page 6) lists the correct orifice size to use at
different altitudes. See Example 1 to determine the unit 
rating and orifice size.
• After changing the orifices, it is required that you
measure the gas input rate by clocking the gas meter 
and using the local gas heating value. See Step 6 and 
Example 2 below.
• Observe the action of the burners. Make sure there is
no yellowing, lifting or flashback of the flame.
WARNING:
The	 reduction	 of	 input	 rating	 necessary	 for	 high	
altitude	installation	may	only	be	accomplished	with	
factory	supplied	orifices.	DO	NOT	attempt	to	drill	out	
orifices	in	the	field.	Improperly	drilled	orifices	may	
cause	fire,	explosion,	carbon	monoxide	poisoning,	
personal	injury	or	death.
1. Obtain the gas heating value from the gas supplier (HHV).
2. Verify that the gas supply line is at the correct supply pressure 
and that the supply pressure is within the allowable unit limits 
listed on the unit rating plate.
3. Shut off all other gas fired appliances.
4. Start the unit in heating mode and allow it to run for at least 
three minutes.
5. Using an in-line flow meter, measure the gas flow rate through
the supply line to the unit. Convert the reading into cubic feet 
per hour. Refer to the meter manufacturer’s instructions, or 
the gas supplier for more information.
6. Multiply the gas flow rate in cubic feet per hour by the heating
value of the gas in Btu per cubic foot to obtain the firing rate in 
Btu per hour. See Example 2 below. 
The manifold pressure
must be set to the appropriate value for your installation.
Adjustments to the firing rate can be made by adjusting
the gas manifold pressure.
CHECKING THE MANIFOLD PREssURE
The manifold pressure can be measured by installing a pressure 
gauge or U-tube manometer to the OUTLET end of the gas 
valve as follows:
1. Turn off all electrical power to the appliance.
2. Shut OFF the gas supply at the manual shutoff valve located 
outside of the appliance.
3. Using a 3/16” Allen wrench, remove the manifold pressure tap
plug located on the outlet side of the gas valve. See Figure 
2 (page 5).
4. Install an 1/8” NPT pipe thread fitting, that is compatible with
a Manometer or similar pressure gauge.
5. Connect the Manometer or pressure gauge to the manifold
pressure tap. Turn gas supply on at manual shutoff.
6. Set the room thermostat above room temperature to start the
furnace.
7. Allow the unit to operate for 3 minutes and then check the
manifold pressure. For LP gas installations, the manifold 
pressure should be set to approximately 9.5” WC. If the manifold 
pressure is not set to the appropriate pressure, then it must 
be adjusted.
ADjUsTING THE MANIFOLD PREssURE
NOTE 1: The new valve LP regulator springs must be adjusted 
to the proper input firing rates or manifold settings. Both HIGH 
and LOW fire inputs should be checked. Always inspect the unit 
rating label to determine the correct (0-2,000 ft) factory setting. 
See Table 4 (page 6).
