Specifi cations and illustrations subject to change without notice and

without incurring obligations. Printed in U.S.A. (03/09)

Figure 18. Wire Routing Diagram

Wire Routing Instructions

Low Voltage Wiring

Bring thermostat wiring into Compartment B .

Route out at hole 7 to low voltage access hole
8 .

Make appropriate connections at location 9 .

High Voltage Wiring

Bring Branch Circuit wiring into Compartment A

Route through FMC 1 through conduit 2 to
disconnect 3 .

After disconnect, route wiring back through
conduit 2 to compartment A .

Then route wires through FMC 4 to the unit
control panel access 5 and make ground and
power connections at location 6 .

ANCHOR CONDUIT SECURELY TO BASERAIL