Reznor PDH Option - Installation - Venting Instructions User Manual

Page 7

background image

Form I-PDH-V, P/N 211409R2, Page 7

FIGURE 6 - Attaching

Double-Wall (Type

B) Vent Pipe to the

Heater

FIGURE 6 - STEP 1

Place a continual 1/4” bead

of silicone sealant around the

circumference of the venter

outlet collar.

FIGURE 6 - STEP 2

Slide the double-wall pipe over the collar so that the collar

is inside the inner pipe. Push the double-wall pipe tight to

the heater cabinet. To secure the connection, spaced equal

distance around the pipe, drill and insert three 3/4” long

sheetmetal screws through the pipe and into the collar. Do

not over tighten the screws.

NOTE: Double-wall (Type

B) vent pipe may only be

used if at least 75% of

the equivalent length of

the vent run is vertical.

See vent pipe length on

page 2.

Do STEP 2 immediately

after STEP 1.