Form I-PDH-V, PN 211409R2, Page 4

Venting Requirements (cont’d)

FIGURE 2 - Horizontal Vent Terminal (

NOTE: Read all measurements; drawing is not proportional.)

Approved clearance thimble is required when flue pipe extends through combustible

materials. Follow the requirements of the thimble and/or the vent pipe manufacturer.

Pitch flue pipe down

toward outlet 1/4” per foot

for condensate drainage.

(NOTE: Slope applies to entire horizontal vent run.)

6” (152 mm)

Minimum

Wall

Roof or Building Overhang

3 ft (1M)

Minimum

PDH Sizes 75-225

4 ft (1.2M) minimum;

PDH Sizes 250-400A

6 ft (1.8M) minimum

Reznor (Option CC1)

or Equivalent Vent Cap -

Note positions of vent

cap openings (shaded

areas).

Parapet or

Adjoining Building

Vent Pipe Run

(Comply with

Requirements

No. 1 and 2

on pages 1-2.)

*Follow the instructions in Addendum pages 5-6, to join the double-wall vent terminal

section to a single-wall vent pipe run and to the vent cap. If vent run is Category III,

make secure,sealed joint that best suits type of Category III pipe being used.

6” (152mm) Minimum

*Double-Wall (Type B)

Vent Pipe

*Follow the instructions in Addendum pages 5-7, to join the double-wall vent terminal

section to a single-wall vent pipe run and to the vent cap. If vent run is double-wall (Type

B), join to terminal section following pipe manufacturer’s instructions. If vent run is

Category III, make secure, sealed joint that best suits type of Category III pipe being used.

Roof -

pitched

from

0 to 45°

Approved clearance thimble is required

when flue pipe extends through combustible

materials. Follow the requirements of the

thimble and/or the vent pipe manufacturer.

Vertical flue extension must be 6” (152mm)

higher than anticipated snow depth but no

less than 2 ft (610mm) above the roof.

Roof Flashing

(field supplied)

6” (152mm) minimum

Parapet or

Adjoining Building

PDH Sizes 75-225

4 ft (1.2M) Minimum;

PDH Sizes 250-400A

6 ft (1.8M) Minimum

*Double-Wall

(Type B) Vent Pipe

Reznor (Option CC1)

or equivalent vent cap

Vent Pipe (Comply with Requirements

No. 1 and No. 2 on pages 1- 2.)

FIGURE 3 - Vertical Vent Terminal (

NOTE: Read all measurements; drawing is not proportional.)

Vertical Vent Terminal