Form I-PDH-V, PN 211409R2, Page 2

2. Vent Pipe Diameter and Length

Use only one diameter of vent pipe on an installation.

Minimum vent length is 3 feet (1M).

TABLE 1 - Vent Pipe Diameter and Length for Horizontal or Vertical Vent

Vent pipe diameters and maximum vent lengths in

TABLE 1 apply to either a horizontal

or a vertical vent. Add

all straight sections and equivalent lengths for elbows. The total

combined length must not exceed the

Maximum Vent Length.

Venting

Requirements

(cont’d)

3. Venter (Flue) Outlet

TABLE 2 - Venter

Outlet Size

Venter Outlet Attachment Requirements:

Depending on the size of vent pipe as determined in Requirement No. 2, attach either

the vent pipe directly to the collar or a taper-type connector (See

TABLE 1).

FIGURE 1 - Venter

Outlet Location

Venter

Outlet

Sizes 75-150

16-13/16” (427mm)

Sizes 175-400A

17-1/4” (438mm)

Sizes 75-150

20-3/4” (527mm)

Sizes 175-400A

31” (787mm)

NOTE: Clearance from

vent connection must

be 18” (457mm).

Cabinet

Size

PDH

Vent Pipe

Diameter

Maximum Vent

Length

Equivalent

Straight Length

for 90° Elbow

Equivalent

Straight Length

for 45° Elbow

Field-supplied taper-

type connection

required at the venter

outlet

inches

mm

feet

M

feet

M

feet

M

A

75

4

102

30

9.1

4

1.2

2

0.6

None

100

4

102

40

12.2

5

1.5

2.5

0.8

None

B

125

4

102

40

12.2

5

1.5

2.5

0.8

None

150

5

127

35

10.7

5

1.5

2.5

0.8

None

C

175

5

127

35

10.7

5

1.5

2.5

0.8

None

200

5

127

50

15.2

5

1.5

2.5

0.8

None

225

5

127

50

15.2

5

1.5

2.5

0.8

None

D

250

5

127

50

15.2

5

1.5

2.5

0.8

6” to 5” (152 to 127mm)

taper-type reducer

300

6

152

50

15.2

5

1.5

2.5

0.8

None

E

350

6

152

50

15.2

7

2.1

3.5

1.1

None

7

178

50

15.2

4.5

1.4

2.25

0.7

6” to 7”(152 to 178mm)

taper-type increaser

400A

6

152

50

15.2

8

2.4

4

1.2

None

7

178

50

15.2

5

1.5

2.5

0.8

6” to 7”(152 to 178mm)

taper-type increaser

Cabinet Size

A

B

C

D

E

Model PDH

75

100

125

150

175

200

225

250

300

350 400A

Venter Outlet

Diameter

4 inches

5 inches

6 inches

102 mm

127 mm

152 mm

Side View