beautypg.com

Reznor PDH Option - Installation - Venting Instructions User Manual

Page 3

background image

Form I-PDH-V, P/N 211409R2, Page 3

5. Vent System

Support

Support horizontal runs every six feet (1.8M). Support vertical runs of Category III

or Type “B” double-wall vent pipe in accordance with the requirements of the pipe

manufacturer. Support single-wall vertical pipe in accordance with accepted industry

practice. Do not rely on the heater for support of either horizontal or vertical vent pipe.

Use non-combustible supports on vent pipe.

Do not enclose vent pipe or place pipe closer than 6” (152mm) to combustible material.

On all Model Sizes, any length of single-wall vent pipe exposed to cold air or run

through an unheated area or an area with an ambient temperature of 45°F or less must

be insulated along its entire length with a minimum of 1/2” foil-faced fiberglass, 1-1/2#

density insulation.
Where extreme conditions are anticipated, install a means of condensate disposal.

The vent terminal pipe

must be double-wall (Type B) vent pipe. Heaters must be

equipped with a Reznor vent cap or equivalent. A different style vent cap could cause

nuisance problems or unsafe conditions. The vent cap must be the same size as the

vent pipe.
See

TABLE 3 and FIGURE 2 for requirements of a horizontal vent terminal. See FIG-

URE 3 for requirements of vertical vent termination.

4. Vent System Joints

and Sealing

Vent system joints depend on the type of pipe being used (See “Type of Vent Pipe”,

Requirement No. 1, page 2).
• If using single wall, 26-gauge or heavier galvanized pipe, secure slip-fit

connections using sheetmetal screws or rivets. Seal all joints and seams of single-

wall vent pipe inside the building with aluminum tape or silicone sealant.

• If using Category III vent pipe, follow the pipe manufacturer’s instructions for

joining pipe sections. When attaching Category III pipe to the venter outlet and

to the double-wall (Type B) vent terminal, make secure, sealed joints following a

procedure that best suits the style of Category III pipe being used.

• When using double-wall (Type B) vent pipe, follow the pipe manufacturer’s

instructions for joining pipe sections.

For joining double-wall pipe to the heater collar, single-wall pipe, and vent cap,

follow the illustrated instructions in the Addendum Section,

pages 5-7.

7. Condensation

8. Vent Terminal (Pipe

and Vent Cap -

See FIGURE 2 or

FIGURE 3.)

6. Clearance

TABLE 3 - Horizontal

Vent Terminal

Clearances

Structure

Minimum Clearances for Vent Termination

Location (all directions unless specified)

Forced air inlet within 10 ft (3.1M)

3 ft (0.9M) above

Combustion air inlet of another appliance

6 ft (1.8M)

Door, window, or gravity air inlet

(any building opening)

4 ft (1.2M) horizontally
4 ft (1.2M) below
1 ft (305mm) above

Electric meter, gas meter*, and relief

equipment

U.S. - 4 ft (1.2M) horizontally

Canada - 6 ft (1.8M) horizontally)

Gas regulator *

3ft (0.9M) horizontally

Adjoining building or parapet

6 ft (1.8M)

Adjacent public walkways

7 ft (2.1M) above

Grade (ground level)

1 ft (0.9M) above**

*Do not terminate the vent directly above a gas meter or service regulator.
** Consider local snow depth conditions. The vent must be at least 6” (152mm) higher than

anticipated snow depth.

Maintain a minimum clearance of 6 inches (152mm) from the wall to the vent terminal

cap for stability under wind conditions.
Products of combustion can cause discoloration of some building finishes and dete-

rioration of masonry materials. Applying a clear silicone sealant that is normally used

to protect concrete driveways can protect masonry materials. If discoloration is an

esthetic problem, relocate the vent or install a vertical vent.

Horizontal Vent

Terminal