Reznor VP Series Option - Installation - Combustion Air Kits User Manual
Page 3

3
Hose Connection
Step 3: After attaching the fresh air inlet plate,
connect the flexible hose. Using a No. 2 flat
screwdriver, tighten the hose clamp screw to make a
secure connection. Re-commission the burner to
ensure correct operation.
Step 2: Do not remove the orifice plate. Attach the
fresh air inlet plate over the fan studs and refasten with
the original nuts, making sure not to cross thread the
fan stud fixings.
Section 2
VPS Four Fixing Fan Procedure
Step 1: Using a No.2 cross head screwdriver,
remove the four screws securing the fan orifice plate.
Step 2: Do not remove the orifice plate. Attach the
fresh air inlet plate on top of the orifice plate and
refasten with the original screws, making sure not to
cross thread the fan fixings.
Section 1
VPS Three Fixing Fan Procedure
Step 1: Using an 8mm wrench remove the nuts securing
the fan orifice plate.
For details of fresh air ductwork to the exterior
please refer to the appropriate instruction manual
for the heater being converted.