INSTALLATION INSTRUCTIONS (cont'd)

7. Install Polytube (See Figure 9)

The polytube adapter is now completed and ready for the field-supplied poly-

tube. Slip the end of the polytube over the collar under the tightening band. Be

sure that the air delivery holes are pointed in the proper direction. Fasten the

band over the polytube by tightening the adjusting screw.
Polytubes are normally supplied as a tube which is open at both ends. The end

opposite the heater must be closed to permit the tube to inflate.
For greenhouse floor-mounted installations, the polytube is usually allowed to

rest on the floor underneath the grow tables.

8. Attach Label

For future reference, attach the "Polytube Holes Location" label on the side

panel of the adapter. (See recommended location in the Dimension Drawing on

page 1.) Wipe the surface of the panel with a clean dry cloth. Remove the

backing from the label and adhere it to the adapter.

9. Installation Checks

When the installation is completed, the motor load and discharge air temperature

should be checked. Consult the installation manual supplied with the heater for

information on checking motor load and how to make blower speed adjust-

ments.
Use a temperature measuring device to check the discharge air temperature.

Discharge

Panel

Band with

Adjusting

Screw

Polytube

Ductwork

Figure 9 - Attach Discharge

Panel and Polytube Ductwork

Check the air temperature at a location in the tube, six to eight

feet way from the heater. A temperature rise range of 55° to

65° F is recommended. Following the instructions in the heater

manual, adjust the speed of the blower to achieve the desired

range while maintaining motor current draw below the full load

amperes shown on the motor rating plate.

POLYTUBE SELECTION - Polytube selection is the responsibility of the installer. Different grades, hole positions, hole sizes, and lengths are

available. Some local code authorities require that polytube material be a listed material. Consult code authority having jurisdiction and polytube

supplier to determine the appropriate polytube material and recommended methods of suspension. Polytubing can be obtained from a supply

distributor such as FOF Products, Inc., P. O. Box E, 1505 Racine Street, Delavan,WI 53005; Acme Engineering company, P. O Box 978, Muskogee,

OK 74402; or any local greenhouse supply distributor.
The total open or free area of the polytube is important. Polytube suppliers have a great deal of flexibility in placement and sizing of holes. Too small

of a free area will cause overheating. Excessive open area may not permit the tube to inflate. See the table below for a guide in hole size and location.

Spacing and hole size may be varied, but free area must not be less than shown for your heater size.

Conversion Table

(Diameter to Area)

Diameter

Area

of the Hole

of the Hole

(inches)

(square inches)

2-1/2

4.91

2-1/4

3.98

2

3.14

1-7/8

2.76

1-1/2

1.76

1

0.785

WARNING: Optional

polytube adapters are to

be used only on units

equipped with a blower.

At no time should the free

area in the polytube be less

than the listed minimum.

Failure to comply with

this warning could result

in severe personal injury,

death, and/or property

damage.

CFM at Polytube

M inimum Free

Suggested Hole Sizes and Locations

Size

.25"

Diameter

Area (square

Length of Polytube

ESP

(inches)

Inches)

50 Ft

75 Ft

100 Ft

125 Ft

150 Ft

Number

37p airs

75 pairs

75 pairs

75

925

18

110

Diameter

1-1/2"

1"

1"

Sp acing

16"

12"

16"

Number

50 p airs 50 pairs 100 pairs

94 pairs

100 1235

18

145

Diameter

1-1/2"

1-1/2"

1"

1"

Sp acing

12"

18"

12"

16"

Number

40 p airs 60 pairs

60 pairs

125 p airs

125 1540

18

185

Diameter

1-7/8"

1-1/2"

1-1/2"

1"

Sp acing

15"

15"

20"

12"

Number

40 p airs 60 pairs

60 pairs

125 p airs

130 1600

24

190

Diameter

1-7/8"

1-1/2"

1-1/2"

1"

Sp acing

15"

15"

20"

12"

Number

50 p airs 50 pairs

75 pairs

75 pairs

75 p airs

165 2035

24

240

Diameter

1-7/8"

1-7/8"

1-1/2"

1-1/2"

1-1/2"

Sp acing

12"

18"

16"

20"

24"

Number

42 p airs 42 pairs

60 pairs

60 pairs

100 pairs

200 2465

24

300

Diameter

2-1/4"

2-1/4"

1-7/8"

1-7/8"

1-1/2"

Sp acing

14"

21"

20"

25"

18"

Number

40 p airs 60 pairs

60 pairs

60 pairs

60 p airs

250 3085

24

360

Diameter

2-1/2"

2"

2"

2"

2"

Sp acing

15"

15"

20"

25"

30"

Number

75 p airs 75 pairs

75 pairs

75 pairs

75 p airs

300 3700

24

425

Diameter

2"

2"

2"

2"

2"

Sp acing

9"

12"

16"

20"

24"

Number

60 p airs 60 pairs

60 pairs

100 p airs 100 pairs

400 4935

24

550

Diameter

2-1/2"

2-1/2"

2-1/2"

1-7/8"

1-7/8"

Sp acing

10"

15"

20"

15"

18"

Holes

(800) 695-1901, www.RezSpec.com

©2014 Reznor, LLC. All rights reserved.

Printed in the U.S.A.

MANUFACTURER OF GAS, OIL, ELECTRIC HEATING AND VENTILATING SYSTEMS

Trademark Note: Reznor

®

is registered in the United States and other countries.

0514 POD OG Form I-B-PF (Version 0.1)