beautypg.com

Reznor UDAP-CV with option AV6 Option - Installation - Common Vent User Manual

Page 4

background image

Form I-UD-V-CV, P/N195677R5, Page 4

2.5 SECTION 1

- Vent System

Support

2.6 SECTION 1 -

Vent Terminal

2.3 SECTION 1 - Vent System Joints/Sealing

Vent system joints depend on the type of pipe:

Single-wall pipe, 26-gauge or heavier galvanized, secure each slip-fit

connection with three sheetmetal screws or rivets. When connecting the

single-wall pipe to the Type B double-wall pipe, use an adapter made by

the Type B double-wall pipe manufacturer for connection of their Type B

double-wall pipe to single-wall pipe. Follow the Type B double-wall pipe

manufacturer’s instructions.

Type B double-wall pipe, follow the pipe manufacturer’s instructions for

joining and securing the pipe sections. If Type B double-wall pipe is con-

nected to the vent collar on the Model UDAP-CV, use an adapter made by

the Type B double-wall pipe manufacturer for that purpose. Follow the Type

B double-wall pipe manufacturer’s instructions.

CAUTION: Exceeding the specified vent pipe diameter and

length may result in condensate forming in the vent pipe.

On units with long vent runs (over 50% of maximum vent length allowed)

or installed in low ambient conditions (below 50°F), it is recommended

that the vent pipe be fitted with a tee, a drip leg, and a cleanout cap to pre-

vent moisture in the vent pipe from entering the unit. The drip leg should

be inspected and cleaned out periodically during the heating season.
A single-wall vent pipe run exposed to cold air or run through an unheated

area, or an area with an ambient temperature of 50°F or less,

must be insu-

lated along its entire length with a minimum of 1/2” foil-faced fiberglass, 1-

1/2# density insulation.
The horizontal vent run

must be pitched down toward the terminal end

1/4” per foot for condensate drainage. The slope applies to the entire length of

the horizontal vent run. Failure to pitch the vent run properly may damage the

heater due to condensate running back into the unit.

Use non-combustible supports on vent pipe. Support lateral runs every six feet

(1.8M). Support vertical runs of Type B double-wall vent pipe in accordance

with the requirements of the pipe manufacturer. Support lateral single-wall pipe

in accordance with accepted industry practices. Do not rely on the heater for

support of either horizontal or vertical vent pipe.

The vent terminal should be a minimum of six feet (1.8M) from adjoining build-

ings. The vent terminal should be six inches (152mm) higher than the antici-

pated snow depth but no less than two feet (610mm) above the roof. Where

the vent extends through the roof, a clearance thimble is required when the

flue pipe extends through combustible materials; follow the requirements of the

double-wall pipe manufacturer.
Terminate with a Reznor Option CC1 vent cap.

Maintain 6 inches (152 mm) clearance between a single-wall vent pipe and

combustibles.
For Type B double-wall vent pipe, follow the pipe manufacturer’s recommenda-

tions for clearance to combustibles.

2.7 SECTION 1 -

Clearance to

Combustibles

2.0 SECTION 1 -

Requirements

and

Instructions

for Venting

a Single

Category I

Model UDAP-

CV (cont’d)

2.4 SECTION 1 -

Condensation