MICROTEL

CellStat

TM


36

(7.7" wide 8.8" high x 4" deep)

Suitable for Wall or Panel Mounting

Battery Mounted Separately

Nema 4 Fiberglass Case with Hard Cover

(12” Wide, 15.5” High, 6.6” Deep)

Nema 12 Fiberglass Case with Hard Cover

Nema 12 Fiberglass Case with Clear Cover

(9” Wide, 10.5”High, 6.5” Deep)


Weight:

Panel Mount Unit 4 lbs

Nema 12 case: 6 lbs

Full system: 10 lbs


A.6 Speech

Type:

Nonvolatile, with Automatic Gain Control of user-
recorded messages.


Resident vocabulary for programming
prompts/status reports, and User-recorded messages
for System Greeting and each Fault Input.


Recordable Message Lengths: 10 Seconds System Greeting

6 Seconds Each Fault Message


A.7 Fault Inputs

Type:

Isolated Dry Contact, Normal Open or Normal
Closed, Non-Latched, optional Alarm-Clear

Sensing

frequency:

1

Hz


Sensing current:

Closed circuit sees a 10 mA (nominal),
10 millisecond-duration pulse, once every second.


Sensing voltage:

Open circuit sees 5 Volts (nominal)


Max. Loop Resistance:

10 killiohms


Max. Loop Capacitance:

100,000 picofarads


Isolation:

1500 Volts, transformer and optical isolation.


Fault Integration Delay:

00 – 99 seconds


AC Power Fail Detect:

Internal circuit, configurable enable and alarm delay