beautypg.com

Table 2 — refrigerant charge – Carrier Centrifugal Liquid Chiller 19EX User Manual

Page 10

background image

Table 1 — 17/19EX Heat Exchanger, Economizer/Storage Vessel, Piping, and Pumpout Unit Weights*

COOLER

SIZE†

COOLER

TOTAL

WEIGHT

COOLER
CHARGE

ECONOMIZER/

STORAGE

VESSEL**

ECONOMIZER

REFRIGERANT

MISCELLANEOUS

PIPING

PUMPOUT

UNIT

Dry

Operating††

Refrigerant

Water

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

gal

kg

L

31

14,173

6 429

17,518

7 946

1,540

699

1,810

217

821

821

7,169

3252

610

277

820

372

210

95

32

14,538

6 594

18,117

8 218

1,640

744

1,944

233

882

882

33

14,904

6 760

18,722

8 492

1,740

789

2,078

249

943

943

41

21,674

9 831

26,120

11 848

1,900

862

2,441

293

1 107

1 107

7,169

3 252

610

277

1,095

497

42

22,019

9 988

26,736

12 127

2,000

907

2,575

309

1 168

1 168

43

22,364

10 144

27,322

12 393

2,100

953

2,709

325

1 229

1 229

44

23,841

10 814

29,836

13 533

2,190

993

3,285

394

1 490

1 490

45

25,032

11 354

30,790

13 966

2,260

1 025

3,006

361

1 363

1 363

7,900

3 583

840

381

1,149

521

46

25,529

11 580

31,658

14 360

2,360

1 070

3,192

383

1 448

1 448

47

26,025

11 805

32,496

14 740

2,460

1 116

3,378

405

1 532

1 532

48

28,153

12 770

36,053

16 353

2,540

1 152

4,173

500

1 893

1 893

CONDENSER

SIZE†

CONDENSER TOTAL WEIGHT

CONDENSER CHARGE

Dry

Operating††

Refrigerant

Water

lb

kg

lb

kg

lb

kg

lb

gal

kg

L

31

10,454

4 742

13,022

5 907

950

431

1,613

193

732

732

32

10,809

4 903

13,514

6 130

950

431

1,750

210

794

794

33

11,164

5 064

14,000

6 350

950

431

1,886

226

855

855

41

13,768

6 245

16,999

7 711

1,090

494

2,146

257

973

973

42

14,118

6 404

17,498

7 937

1,090

494

2,282

274

1 035

1 035

43

14,468

6 563

17,978

8 155

1,090

494

2,419

290

1 097

1 097

45

16,676

7 564

20,800

9 435

1,400

635

2,720

326

1 234

1 234

46

17,172

7 789

21,489

9 747

1,400

635

2,908

348

1 319

1 319

47

17,669

8 015

22,178

10 060

1,400

635

3,096

371

1 404

1 404

51

17,188

7 796

20,993

9 522

1,100

499

2,707

325

1 228

1 228

52

17,848

8 096

21,923

9 944

1,100

499

2,964

355

1 344

1 344

53

18,400

8 346

22,682

10 288

1,100

499

3,178

381

1 442

1 442

55

20,725

9 401

25,598

11 611

1,420

644

3,453

412

1 566

1 566

56

21,663

9 826

26,896

12 199

1,420

644

3,808

457

1 727

1 727

57

22,446

10 181

27,980

12 691

1,420

644

4,105

492

1 862

1 862

*If a machine configuration other than 2-pass, 150 psig (1034 kPa), NIH waterbox configuration is used, refer to Tables 3

and 4 to obtain the additional dry and water weights that must be added to the values shown in this table.

†Cooler and condenser weights shown are based upon 2-pass, nozzle-in-head (NIH) waterboxes with 150 psig (1034 kPa)

covers. Includes components attached to cooler, but does not include suction/discharge, elbow, or other interconnecting
piping.

**Dry weight includes all components attached to economizer: Covers, float valves, brackets, control center (31 lb [14 kg]),

and power panel (20 lb [9 kg]). Dry weight does not include compressor weight, motor weight, or pumpout condensing unit
weight. The pumpout condensing unit weight is 210 lb (95 kg). For compressor and motor weights, refer to Tables 6, 7, 8,
10A, and 10B.

††Operating weight includes the sum of the dry weight, refrigerant weight, and water weight.

Table 2 — Refrigerant Charge

HEAT EXCHANGER SIZE

COOLER CHARGE

CONDENSER CHARGE

ECONOMIZER CHARGE

TOTAL REFRIGERANT

CHARGE*

Cooler

Condenser

lb

kg

lb

kg

lb

kg

lb

kg

31

31

1540

699

950

431

610

277

3100

1 406

32

32

1640

744

950

431

3200

1 452

33

33

1740

789

950

431

3300

1 497

41

41

1900

862

1090

494

3600

1 633

42

42

2000

907

1090

494

3700

1 678

43

43

2100

953

1090

494

3800

1 724

44

51

2190

993

1100

499

3900

1 769

44

52

2190

993

1100

499

3900

1 769

44

53

2190

993

1100

499

3900

1 769

45

45

2260

1 025

1400

635

844

381

4500

2 041

46

46

2360

1 070

1400

635

4600

2 087

47

47

2460

1 116

1400

635

4700

2 132

48

55

2540

1 152

1420

644

4800

2 177

48

56

2540

1 152

1420

644

4800

2 177

48

57

2540

1 152

1420

644

4800

2 177

*Total machine refrigerant charge includes the cooler, condenser, and economizer.

NOTE: Regulations mandate that machine shipping charge is limited to 7500 lb (3402 kg).

10

This manual is related to the following products: