beautypg.com

LAARS Pennant PNCV (Sizes 500-2000) - Install and Operating Manual User Manual

Page 51

background image

Pennant

(500-2000)

Page 51

controller setup. Contact your Laars representative to

discuss possible remedies.

8.4 Short Cycling — Water Heater

Short cycling will generally occur only in

combination space heating and water heating

applications when the water heater is operating in the

space-heating mode. Because the Pennant is a stage-

fired water heater and its input will reduce when there

is a reduction in heating load, short cycling is greatly

reduced. If the heating load drops below the minimum

input of the water heater for an extended period, the

water heater will have a tendency to short cycle. If

short cycling is frequently experienced, regardless of

the control’s attempt to limit it, the heating load should

be redistributed to control it. See

Section 6.3

regarding

controller setup.

If short cycling occurs in a water heater

application, it is probably caused by undersized

piping between the water heater and the storage tank

or by some other factor that restricts proper water

flow through the water heater. The cause should be

determined and corrected.

8.5 High Gas Consumption

Appliances operating with an improper air/

fuel ratio are very inefficient and consequently, have

very high gas consumption. Because efficiency is

high when the CO

2

is high (or O

2

is low), appliances

operating with low CO

2

or high O

2

(especially LP

appliances) consume more gas. Adjust the CO

2

or O

2

for optimum efficiency. If no combustion analyzing

equipment (CO

2

or O

2

) is available then a proper

adjustment of the air/fuel ratio (CO

2

or O

2

) cannot be

accomplished. However, by briefly sniffing the flue

gases it is possible to determine if the CO

2

or O

2

is

within the proper range. No significant flue gas odor

should be detected when combustion is proper. A

strong piercing smell indicates poor combustion and

generally a lean mixture - low CO

2

or high O

2

. The

CO

2

should be 8% at high fire. To check the CO

2

, first

verify that the supply gas pressure is within 5" to 13"

w.c. (1.2 to 3.2 kPa) With the Pennant running with all

stages firing, set the air box pressure to 1.5" w.c. (0.37

kPa) (as a starting point), by adjusting the air shutter(s)

at the bottom of the fan(s). Check the CO

2

, and adjust

the air shutters if further adjustment to the CO

2

is

needed. Sizes 1250 to 2000 have two blowers and two

air chambers (boxes). The pressure of each air box

must be equal when the final adjustment is made.

8.6 Troubleshooting the Temperature

Control

See

Table 12.

8.7 Troubleshooting Pennant Controls

The Pennant series consists of two 2-stage

SECTION 8.

Trouble Shooting

8.1 Resolving Lockouts

There are many causes of lockouts. The three

most common causes are: (1) inadequate gas supply,

(2) poor combustion, (3) ignitor failure.

1. Inadequate gas supply: Before proceeding, ensure

that the gas supply has not been shutoff or the LP

tank (LP boilers) is not empty. Then, restart the

boiler and observe the operational cycle. After

a 15-second fan pre-purge, the ignitor will heat

up for 20 seconds, and then the unit will light.

If it does not, check the gas supply pressure to

the appliance, after resetting the appliance and

attempting another start-up. The gas pressure

to the appliance must be above 5" w.c. (1.2kPa)

throughout the entire start-up cycle. If it is not,

correct the supply problem (check gas valves or

supply piping). If the supply pressure is adequate,

consult the factory for assistance.

2. Poor Combustion: Poor combustion should be

suspected if there is a strong flue gas odor. The

odor may result from an improper gas/air ratio

(high or low O

2

or CO

2

). Pennant appliances

operate best with 45% excess air (8% CO

2

on

natural gas, 9.2% CO

2

on LP). Check the CO

2

of

the appliance and adjust if necessary.

3. Ignitor failure: If the boiler goes through a

normal start cycle but combustion does not

occur, ignitor failure should be suspected. Check

the ignitor by unplugging the ignitor plug and

measuring the ignitor resistance. It should be

50-80 ohms. If the resistance is not 50-80 ohms,

replace the ignitor. If the resistance is correct,

reset the boiler and check for 120 VAC at the

ignitor plug during the start cycle. If there is no

voltage, replace the faulty ignitor wire harness or

the ignition control.

8.2 Delayed Ignition — Possible Causes

A defective burner can cause a delayed ignition.

If the gas supply pressure is proper and the gas

valves are functioning properly, then burners should

be inspected. There should be no distortion or

perforations in the burners outside of the active burner

port area. Replace if indicated.

8.3 Short Cycling — Boiler

Because the Pennant is a stage-fired boiler, and

its input will decrease when there is a reduction in

heating load, short cycling is greatly reduced. If the

heating load drops below the minimum input of the

boiler for an extended period, the boiler will have

a tendency to short cycle. This can be a symptom

of improper control strategy or setpoints, or a load

distribution problem. See

Section 6.3

regarding

This manual is related to the following products: