beautypg.com

Laars heating systems, Page 18 – LAARS Pennant PNCV (Sizes 500-2000) - Install and Operating Manual User Manual

Page 18

background image

LAARS Heating Systems

Page 18

LEGEND

CHECK VALVE

THERMOMETER

TEMPERATURE
SENSOR

GLOBE VALVE

EXPANSION TANK
WITH AIR SCOOP AND

AUTO AIR VENT

3-WAY VALVE

VALVE

CAUTION: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND VALVING, CHECK
WITH LOCAL CODES AND ORDINANCES FOR
ADDITIONAL REQUIREMENTS.

PRESSURE REDUCING VALVE
W/ FAST FILL BYPASS

PURGE

VALVE

PUMP

PRIMARY/SECONDARY MANDITORY FOR ALL
VARIABLE FLOW SYSTEMS

INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM

PIPING & SIZING OF EXPANSION TANK
PER TANK MANUFACTURER'S INSTRUCTIONS

DIMENSION "C" (COMMON PIPING) TO BE FOUR
PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES)

BOILER CIRCUIT PIPING MUST BE EQUAL
TO BOILER WATER CONNECTION SIZE

BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER

DOTTED DEVICES INDICATE ALTERNATE LOCATIONS

PUT BOILER CONTROL SENSOR IN THE SYSTEM

C

PUMP LOCATION FOR PUMP-MOUNTED UNITS

SYSTEM PUMP

MAKE-UP

COLD WATER

SUPPLY

SYSTEM

PUMP LOCATION FOR
NON-PUMP-MOUNTED UNITS

RETURN

SYSTEM

SUPPLY WHEN USING THIS PIPING STYLE.

MINIMUM BOILER INLET WATER TEMPERATURE
MUST BE AT LEAST 120°F.

Figure 7. Hydronic Piping - Primary-Secondary, Reverse-Return.

This manual is related to the following products: