PRIMARY/SECONDARY MANDITORY FOR ALL
VARIABLE FLOW SYSTEMS
INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM
PIPING & SIZING OF EXPANSION TANK
PER TANK MANUFACTURER'S INSTRUCTIONS

DIMENSION "C" (COMMON PIPING) TO BE FOUR
PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES)

BOILER CIRCUIT PIPING MUST BE EQUAL
TO BOILER WATER CONNECTION SIZE

BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER

DOTTED DEVICES INDICATE ALTERNATE LOCATIONS

PUT BOILER CONTROL SENSOR IN THE SYSTEM

C

PUMP LOCATION FOR PUMP-MOUNTED UNITS

SYSTEM PUMP

MAKE-UP

COLD WATER

SUPPLY

SYSTEM

PUMP LOCATION FOR
NON-PUMP-MOUNTED UNITS

RETURN

SYSTEM

SUPPLY WHEN USING THIS PIPING STYLE.

MINIMUM BOILER INLET WATER TEMPERATURE
MUST BE AT LEAST 120°F.

C

ADJUSTMENT PROCEDURE TO MAINTAIN
120°F INLET TEMP:
1. Turn on boiler and open valves A & B.
2. After steady-state operation, if T1 is less than

slowly close valve B until T1 climbs to

120°F.

3. If T1 is greater than 120°F, slowly close

until T1 drops to 120°F.

4. Check after system operating temperature

has stabilized. Make final adjustments.

120°F,

valve A

A

B

T1

B

A

T1

LEGEND

CHECK VALVE

THERMOMETER

TEMPERATURE
SENSOR

GLOBE VALVE

EXPANSION TANK
WITH AIR SCOOP AND

AUTO AIR VENT

3-WAY VALVE

VALVE

CAUTION: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND VALVING, CHECK
WITH LOCAL CODES AND ORDINANCES FOR
ADDITIONAL REQUIREMENTS.

PRESSURE REDUCING VALVE
W/ FAST FILL BYPASS

PURGE

VALVE

PUMP

Figure 5. Hydronic Piping — Multiple Boilers, Low Temperature System.