LAARS Gateway LER - Manual User Manual
Page 8
LAARS Heating Systems
Page 8
LAARS Gateway Startup Guide
Page 8 of 32
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web:
www.laars.com
Toll Free: (800) 900-9276
The Following chart describes S0 – S3 DIP Switch configuration settings for the Mascot II, NeoTherm, and
NeoTherm LC boilers – 1 through 8 units to support BACnet MSTP/IP and Metasys N2 on a Gateway RER. The
Mascot II, NeoTherm, and NeoTherm LC boilers all use the same configuration points list.
See Appendix B.2 for additional configuration DIP switch settings:
For the Mascot II, NeoTherm, and NeoTherm LC boilers to support Modbus TCP on the Gateway RER
B.
LonWorks for the Mascot II, NeoTherm, and NeoTherm LC
The following chart describes S0 – S3 DIP Switch configuration settings for Mascot II, NeoTherm, and NeoTherm LC
boilers to support LonWorks on a Gateway LER. The Mascot II, NeoTherm, and NeoTherm LC units all use the same
configuration points list.
Gateway LER
Gateway S Bank DIP Switches
Profile - FPC-N35
S0
S1
S2
S3
LonWorks Sola 1
Off
Off
Off
Off
LonWorks Sola 2
On
Off
Off
Off
LonWorks Sola 3
Off
On
Off
Off
LonWorks Sola 4
On
On
Off
Off
LonWorks Sola 5
Off
Off
On
Off
LonWorks Sola 6
On
Off
On
Off
LonWorks Sola 7
Off
On
On
Off
LonWorks Sola 8
On
On
On
Off
Gateway RER
Gateway S Bank DIP Switches
Profile – FPC-N34
S0
S1
S2
S3
BACnet IP/BACnet MSTP Sola 1
Off
Off
Off
Off
BACnet IP/BACnet MSTP Sola 2
On
Off
Off
Off
BACnet IP/BACnet MSTP Sola 3
Off
On
Off
Off
BACnet IP/BACnet MSTP Sola 4
On
On
Off
Off
BACnet IP/BACnet MSTP Sola 5
Off
Off
On
Off
BACnet IP/BACnet MSTP Sola 6
On
Off
On
Off
BACnet IP/BACnet MSTP Sola 7
Off
On
On
Off
BACnet IP/BACnet MSTP Sola 8
On
On
On
Off
Metasys N2 Sola 1
Off
Off
Off
On
Metasys N2 Sola 2
On
Off
Off
On
Metasys N2 Sola 3
Off
On
Off
On
Metasys N2 Sola 4
On
On
Off
On
Metasys N2 Sola 5
Off
Off
On
On
Metasys N2 Sola 6
On
Off
On
On
Metasys N2 Sola 7
Off
On
On
On
Metasys N2 Sola 8
On
On
On
On