C-4 Compaq 6000 Series UPS Operation and Reference Guide

Table C-3
Output Specifications

continued

II. Output Voltage

Utility Voltage (VAC)

Nominal Output Voltage

(VAC)

Nominal Output

Voltage on Battery

(VAC)

200

200

204

208

208

204

220

220

230

230

230

230

240

240

230

III. Source of Utility Power

Source

Regulation

Utility power
(normal range)

±

10% of nominal output voltage

(within the guidelines of the Computer Business
Equipment Manufacturers Association)

Utility power
(extended range)

+10% to -15% of nominal output voltage and/or +5/-3%
frequency.
(within the guidelines of the Computer Business
Equipment Manufacturers Association)

Battery power

±

5% of nominal output voltage

IV. Additional Features

Feature

Specification

On-line efficiency

96%

Voltage wave shape while
on battery

Sinusoidal with less than 3% THD @ linear load

Surge suppression

High energy 6500 A peak
(meets the requirements of ANSI C62.41 Category B

(formerly IEEE 587) )

Noise filtering

The input noise suppression is comprised of Normal
Mode Filtering, Common Mode Filtering, or combination
of both.