beautypg.com

Caution, Install outdoor unit, Side or bottom piping – Carrier 40QNQ User Manual

Page 7: Mounting on ground, Mounting on roof

background image

7

point A or B as shown in Fig. 12 or Fig. 13. Drill the hole at a
slope so that the outside end is 1/2 inch (13 mm) lower than inside

end to ensure optimal drainage. Refer to Fig. 14.

Side Or Bottom Piping

Remove the knockout in the unit and drill a 2--1/2 inch (63.5 mm)
hole where the pipe penetrates the structure using the guides given

above.

2.1"

(53.3)

14.9" (378.5)

3.5"

(88.9)

2.8"

(71.1)

2.8"

(71.1)

B

5.1”

(129.5)

13.8" (130.5)

A

2"

(50.8)

7.7" (195.6)

35.4” (899.2)

2.1"

(53.3)

1"

(25.4)

Note: Numbers in ( ) = mm

A09046

Fig. 12 -- 40QNC, QNQ018, 024 Mounting Plate

2"

5.1"

B

A

A09050

Fig. 13 -- 40QNC, QNQ030, 036 Mounting Plate

1/2 in. (13 mm)

Min.

INDOOR

OUTDOOR

A07371

Fig. 14 -- Drill Hole at Slope

4. Relocate drain connection if necessary -- Determine if the

installation requires a left or a right hand drain exit and relo-
cate the drain hose if necessary as shown in Fig. 15.

Drain Hose

Drain Cap

A08362

Fig. 15 -- Drain Hose and Cap Location

NOTE: If the condensate pump accessory is to be used, the drain
hose can be cut to provide space for the space for the condensate
pump reservoir in the back of the unit. The reservoir must be
installed at this time. Please refer to installation instructions
provided with the condensate pump accessory.

5. Place unit on a clean surface until you are ready to connect

the piping and wiring.

INSTALL OUTDOOR UNIT

The outdoor units can be installed on the ground, on the roof, or
mounted on a wall.
NOTE: Install the unit so that the coil does not face into
prevailing winds. If this is not possible and constant wind winds
above 25 mph are expected, use accessory wind baffle. See
installation instructions provided with accessory kit. Wind baffles
should also be used on all units with accessory low ambient
temperature control.

Mounting on Ground

1. Mount unit on a solid level concrete pad.
2. If a heat pump is being installed, use a field-- provided snow

stand or ice rack where prolonged subfreezing temperatures
or heavy snow occurs.

3. Position unit so water or ice from roof does not fall directly

onto unit.

4. On cooling only units, an accessory stacking kit can be used

when units are to be stacked. See installation instructions
provided with the accessory kit.

Mounting on Roof

PERSONAL

INJURY

AND/OR

EQUIPMENT

DAMAGE HAZARD
Failure to follow this caution may result in personal injury

and / or equipment damage.

Be sure unit panels are securely in place prior to rigging.

CAUTION

!

1. Rig the unit. Keep the unit upright and lift using a sling.

Use cardboard or padding under the sling, and spreader bars

to prevent sling damage to the unit. See Fig 16. See Fig. 2
for center of gravity reference

2. Mount unit on a solid concrete pad or platform.
3. Isolate unit and piping from structure
4. If a heat pump is being installed, use a field-- provided snow

stand or ice rack where prolonged subfreezing temperatures
or heavy snow occurs.

5. On cooling only units, an accessory stacking kit can be used

when units are to be stacked. See installation instructions
provided with accessory kit.

A07396

Fig. 16 -- Lifting Unit with Sling

This manual is related to the following products: