SERVICE

!

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Before installing, modifying, or servicing system, main

electrical disconnect switch must be in the OFF

position. There may be more than 1 disconnect switch.

Lock out and tag switch with a suitable warning label.

Pump--down Procedure

The system may be pumped down in order to make repairs on the

low side without losing complete refrigerant charge.

1. Attach pressure gage to suction service valve gage port.
2. Front--seat the mixed phase line valve.

CAUTION

!

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage

or improper operation.
The unit coils hold only the factory--designated amount of

refrigerant. Additional refrigerant may cause units to relieve

pressure through the compressor internal pressure relief valve

(indicated by a sudden rise of suction pressure) before suction

pressure reaches 20 psig. If this occurs, shut off unit

immediately then front--seat the suction valve and remove and

recover excess refrigerant following accepted practices.

3. Start unit and run until suction pressure reaches 5 psig.
4. Shut unit off and front--seat suction valve.
5. Depressurize low side of unit and recover refrigerant fol-

lowing accepted practices.

Filter Drier

Whenever the filter drier is exposed to the atmosphere it must be

replaced. Only use factory specified liquid--line filter driers with
rated working pressures less than 600 psig.
NOTE: Do not install a suction--line filter drier in the mixed phase
line.

Refrigerant Charging

!

WARNING

PERSONAL INJURY AND/OR EQUIPMENT

DAMAGE HAZARD
Failure to follow this warning could result in personal

injury and/or equipment damage.
Wear safety glasses and gloves when handling

refrigerant. Do not overcharge system -- this can cause

compressor flooding.

All units are shipped with the refrigerant charge listed on

nameplate.
NOTE:

Do not vent or depressurize unit refrigerant to

atmosphere. Remove and recover refrigerant following accepted
practices.