These installation instructions cover the installation of the matched
systems listed in table 2.

Parts List

Indoor Unit

The following items are included with the indoor unit:

Table 1 – Installation Materials

Description

Qty

Usage

Wall Mounting

Bracket

1

For Indoor Unit Installation

Screws, 4XL10

2

For Attaching The Remote Control

Holder To The Wall

Screws, 5XL25

5/14*

For Attaching The Mounting Bracket To

The Wall

Remote Control

1

For Controlling Unit

Remote Control

Holder

1

Holder For Remote Control

* 5 screws for unit sizes 18 and 24. 14 screws for unit sizes 30 and 36.

Outdoor Unit

The following items are included with the outdoor unit:

38HDF018-036

A09499

Fig. 5 -- 38HDF018--036

A09500

Fig. 6 -- 38QRF018--036

Model

Filter Drier

Piston

Cap

Pistons*

Flare

Connector

38HDF

n

n

n

n

38QRF

n

n

(qty 2)

n

n

(qty 3)

* Multiple pistons. Quantity varies with size.

Table 2 – Matched Systems

System

Type

Nominal

Capacity

Outdoor

Unit

Indoor

Unit

Cooling

Only

018

38HDF018--- --- ---3

40QNC018024--- --- ---3

024

38HDF024--- --- ---3

40QNC018024--- --- ---3

030

38HDF030--- --- ---3

40QNC030--- --- ---3

036

38HDF036--- --- ---3/5/6

40QNC036--- --- ---3

Heat

Pump

018

38QRF018--- --- ---3

40QNQ018--- --- ---3

024

38QRF024--- --- ---3

40QNQ024--- --- ---3

030

38QRF030--- --- ---3

40QNQ030--- --- ---3

036

38QRF036--- --- ---3/5/6

40QNQ036--- --- ---3

SYSTEM REQUIREMENTS

Clearances

Allow sufficient space around the indoor and outdoor unit for
proper airflow circulation and servicing. Refer to Fig. 3 and Fig. 4

for minimum required clearances.
Piping: Piping and insulation is field supplied.

Piping Lengths

The minimum length between the indoor and outdoor units is 10 ft
(3 m). Refer to table 3 for the maximum lengths allowed.

Table 3 – Maximum Refrigerant Line Lengths

Unit

Size

Max Line

Length ft(m)

Max Elevation (ID

over OD) ft(m)

Max Elevation (OD

over OD) ft(m)

18K

200 (61)

65 (19.8)

200 (61)

24K

200 (61)

65 (19.8)

200 (61)

30K

200 (61)

65 (19.8)

200 (61)

36K

200 (61)

65 (19.8)

200 (61)

Note:For lengths greater than 25 ft (7.6 m), refer to the Duct Free Long

Line Guide.

Pipe Sizes

Refer to table 4 for pipe sizes.

Table 4 – Pipe Sizes

Pipe Sizes (in)

Unit Size

Mix Phase --- in

Vapor --- in

18K

3/8

5/8

24K

3/8

5/8

30K

3/8

3/4

36K

3/8

3/4

Note:Both lines need to be insulated using at least 1/2 inch closed foam

insulation.

Condensate Drain Pipe Sizes

Refer to table 5 for the required sizes.

Table 5 – Drain Pipe Sizes

Unit Size

Outside Diameter --- in

Inside Diameter --- in

18K

5/8

7/16

24K

5/8

7/16

30K

3/4

5/9

36K

3/4

5/9

Note:Do not trap condensate pipe.