Compressor Unit Connections — Extend power leads from
control center (contactor terminals) to compressor terminal box
and make connections as shown in Fig. 4.

Terminals 8 and 9 on motor terminal plate are for internal

protector connections. As shown in Fig. 4, run a wire from ter-
minal 9 to terminal 6 on TB2 in control center and a wire from
terminal 1 on OL2 to terminal 2 on HPS in control center.

Run crankcase heater power wiring into control center.

Connect leads to terminal 5 on pumpout relay and terminal 3
on terminal block TB2. See Fig. 5.

Affix power warning label supplied in the installer’s packet

to fused disconnect which energizes crankcase heater (see unit
label diagram).

CONTROL WIRING — Control circuit power is 115 volts,
energized from an external source or from unit voltage through
field-supplied transformer. Transformer size required is 350 va
for 60 Hz units. External control power source must be
supplied through a 15-amp fused disconnect. Connect control
circuit power leads to terminal block TB2, terminals L1 and
L2. Terminal L2 is neutral potential (ground).
Compressor Protection — The 06D and 07D units are factory
wired for single-pumpout control. Field addition and wiring of
line voltage remote control and liquid line solenoid valve is
required. (See unit Fig. 3 and Fig. 6.) Remote control minimum
contact rating must be 25 va. Solenoid valve must have a
maximum load rating of 50 va holding; 200 va inrush. For
applications with cooling tower, air-cooled or evaporative
condensers, add necessary auxiliary contacts in line between
compressor contactor and terminal A1 on timer. Insert desired
interlocks and overloads between terminals 5 and 9 on terminal
block TB2.

Control wiring may be modified as shown in Fig. 6 for

automatic pumpdown control; remove low-pressure switch
between timer relay and terminal 4 on TB2. Wire low-pressure
switch between terminals 9 and 6 on TB2. Add necessary
auxiliary contacts between compressor contactor and terminal
A1 on timer. Remove wire between terminal 6 on TB2 and
terminal 3 on pumpout relay. Insert required interlocks and
overloads between terminals 5 and 9 on TB2.

Limitations —

Do not use automatic pumpdown control

on direct expansion cooler applications or when compressors
are equipped with pressure-type unloader valves. Pressure
unloader valves have built-in high to low passage which allows
compressor to cycle with automatic pumpdown.

LEGEND

Fig. 4 — Compressor Terminal Diagram

HPS — High-Pressure Switch
OL

Overload Relay

TB

Terminal Block

Factory Wiring

Fig. 5 — 06D/07D Control Box Components and Connections (3-Phase)

LEGEND

NOTES:
1. Factory wiring is in compliance with NEC. Any field modifications or

additions must be in compliance with all applicable codes. Use copper,
copper-clad aluminum for field power supply only.

2. Field power supply wiring must be 75 C minimum.
3. Compressor thermally protected. Three-phase motors are protected

against primary single-phasing condition.

4. Pilot duty control must be field supplied. Minimum contact rating must

be 25 va.

5. 60 Hz units have 120-volt control circuit. 50 Hz units have 230-volt con-

trol circuit. A separate source of supply at the correct voltage must be
field supplied thru a fused disconnect device with a max rating of 15 A
to TB2 connections

(Hot Side) and

(Neutral).

6. Open control circuit disconnect switch for servicing only. Disconnect

must remain closed for crankcase heater to operate.

7. A transformer of the following rating may be field supplied for 60 Hz

units: 350 va.

8. Transformer must be fused and grounded per applicable codes.
9. If any of the original wiring furnished must be replaced, it must be

replaced with 90 C wire or its equivalent.

C

Contactor, Compressor

NEC — National Electrical Code

CH

Crankcase Heater

OL

Overload Relay

CR

Control Relay

OPS — Oil Pressure Switch

FU

Fuse

POR — Pumpout Relay

GND — Ground Connection

SW

Switch

HPS

High-Pressure Switch

TB

Terminal Block

IP

Internal Protector

TM

Timer Motor

LPS

Low-Pressure Switch

TR

Timer Relay

L1

L2