Chapter 2: Reporting codes
NX-8V2 Control Panel Installation Manual
29
Segment 1
1. On enables quick arm.
2. On enables re-exit.
3. On enables automatic bypass.
4. On enables silent keypad panic (overrides the audible panic selection).
5. On enables audible keypad panic.
6. On enables keypad aux 1 (fire panic).
7. On enables keypad aux 2 (emergency panic).
8. On enables keypad multiple code attempt tamper.
Segment 2
1. On enables LED extinguish.
2. On enables require code for bypassing.
3. On enables zone bypassed sounder alert.
4. On enables AC power/low battery sounder alert.
5. On enables bypass toggle.
6. On enables silent autoarm.
7. On enables automatic instant.
8. On enables instant mode toggle.
Segment 3
1. On enables opening and closing reporting.
2. On enables zone bypass reporting.
3. On enables zone restore reporting.
4. On enables zone trouble reporting.
5. On enables zone tamper reporting.
6. On enables cancel reporting.
7. On enables recent closing reporting.
8. On enables exit error reporting.
Segment 4
1. Enables late to close/early to open reporting.
2. On enables auto arm in stay mode.
3. On disables door delays in night mode (applies to NX-1208E/NX1248E keypads).
4. On disables bypass for force arm zones.
5. On enables expander trouble sounder alert.
6, 7, and 8. Reserved.
Segment 5 - Reserved
Location 24 - Entry/exit times
Location 24 has six segments of numerical data. Use this location to program the
entry/exit times (there are two separate entry/exit times).
Segment 1 - Entry time . Entry time used when a delay 1 zone type initiates an entry delay.
Default is 30, valid entries 30 to 255 seconds.
Segment 2 - Exit time 1. Exit time used for all zones designated as delay 1. Default is 60, valid
entries 45 to 255 seconds.