Ansi/sia cp-01 requirements – Interlogix NX-8V2 REV B Installation Manual User Manual
Page 10

ANSI/SIA CP-01 requirements
CP-01 feature descriptions and specifications are listed in Table 9 below. The following are requirements for compliance with
ANSI/SIA CP-01 standards.
Note: Where a conflict exists, UL requirements take precedence over ANSI/SIA requirements.
•
Minimum system requirements:
•
One control panel
•
Two keypads
•
Do not enable remote arming in SIA classified installations.
•
Off premise transmission must be in the SIA format.
•
Do not exceed 1 minute for the abort window and entry delay.
Note: A call-waiting cancel on a noncall-waiting line prevents successful connection to the central station.
Table 9: CP-01 feature descriptions and specifications
CP-O1 feature description
Feature description as shown in
manual
Program
location
Seg/opt Default
CP-01required
setting
Exit 1 delay
24
2
60
45 to 240 seconds
Exit time
Exit 2 delay
24
4
60
45 to 240 seconds
Progress annunciation /
disable - for silent exit
Silent keypad option
93
a
2
All annunciators enabled Allowed (individual
keypads may be disabled)
Exit time restart (reexit)
This feature is not programmable in the panel.
Enabled
Auto stay arm on unvacated
premises
Auto bypass
23
1/3
Enabled
Enabled
Exit time and progress
annunciation/disable for
remote arm
This feature is not programmable in the panel. Exit time and progress are always
enabled.
Enabled (disabled for
remote arming)
Entry 1 delay
24
1
30
30 to 240 seconds
Entry delays
b
Entry 2 delay
24
3
30
30 to 240 seconds
Abort window - for nonfire
zones
Dialer delay
40
8
30
Enabled (may be disabled
by zone/zone type, but no
cancel reports will be sent)
Abort window time - for
nonfire zones
b
Dialer delay
40
8
30
15 to 45 seconds
Abort annunciation
This feature is not programmable in the panel. Flashing cancel LED goes off when
disarming.
Enabled
Cancel annunciation
Cancel 23
3/6
Enabled
Enabled
Duress feature
Duress
44
Disabled
Disabled
Two trips on cross zone
37
5/4
Disabled
Required
Keypad sounds on cross zone trip 39
5
Disabled
Cross zoning
Zone type characteristic
111
3/4
Disabled
Programmable cross zoning
time
Cross zone time
40
6
5 minutes
Allowed
Swinger shutdown
Swinger shutdown count
38
n/a
n/a
For all nonfire zones, shut
down at 1 to 2 trips
Swinger shutdown disable
Swinger shutdown count
38
n/a
Enabled for 1 trip
Allowed
Fire alarm verification
Fire alarm verification time
40
9
Enabled for 1 trip
Required (depends on
panel and sensors)
10
NX-8V2 Control Panel Installation Instructions