Interlogix NX-4V2 Installation Guide User Manual
Page 10
CP-O1 feature description
Feature description as shown in
manual
Program
location
Seg/opt Default
CP-01required
setting
Exit time and progress
annunciation/disable for
remote arm
This feature is not programmable in the panel. Exit time and progress are always
enabled.
Enabled (disabled for
remote arming)
Entry 1 delay
24
1
30
30 to 240 seconds
Entry delays
b
Entry 2 delay
24
3
30
30 to 240 seconds
Abort window - for nonfire
zones
Dialer delay
40
8
30
Enabled (may be disabled
by zone/zone type, but no
cancel reports will be sent)
Abort window time - for
nonfire zones
b
Dialer delay
40
8
30
15 to 45 seconds
Abort annunciation
This feature is not programmable in the panel. Flashing cancel LED goes off when
disarming.
Enabled
Cancel annunciation
Cancel 23
3/6
Enabled
Enabled
Duress feature
Duress
44
Disabled
Disabled
Two trips on cross zone
37
5/4
Disabled
Required
Keypad sounds on cross zone trip 39
5
Disabled
Cross zoning
Zone type characteristic
111
3/4
Disabled
Programmable cross zoning
time
Cross zone time
40
6
5 minutes
Allowed
Swinger shutdown
Swinger shutdown count
38
n/a
n/a
For all nonfire zones, shut
down at 1 to 2 trips
Swinger shutdown disable
Swinger shutdown count
38
n/a
Enabled for 1 trip
Allowed
Fire alarm verification
Fire alarm verification time
40
9
Enabled for 1 trip
Required (depends on
panel and sensors)
Call waiting cancel
Must be programmed as part of
the phone number
0 n/a
n/a
Required
(depends
on
user phone line)
Recent closing
23
3/7
Enabled
Exit error
23
3/8
Enabled
Default changes (from prior
versions):
Power up delay
40
3
60 seconds
a> Refer to your keypad installation manual.
b> Combined abort window time and entry delay must not exceed one minute.
10
NX-4V2 Control Panel Installation Instructions