Interlogix NX-4V2 Installation Guide User Manual

Page 10

background image

CP-O1 feature description

Feature description as shown in
manual

Program
location

Seg/opt Default

CP-01required

setting

Exit time and progress
annunciation/disable for
remote arm

This feature is not programmable in the panel. Exit time and progress are always
enabled.

Enabled (disabled for
remote arming)

Entry 1 delay

24

1

30

30 to 240 seconds

Entry delays

b

Entry 2 delay

24

3

30

30 to 240 seconds

Abort window - for nonfire
zones

Dialer delay

40

8

30

Enabled (may be disabled
by zone/zone type, but no
cancel reports will be sent)

Abort window time - for
nonfire zones

b

Dialer delay

40

8

30

15 to 45 seconds

Abort annunciation

This feature is not programmable in the panel. Flashing cancel LED goes off when
disarming.

Enabled

Cancel annunciation

Cancel 23

3/6

Enabled

Enabled

Duress feature

Duress

44

Disabled

Disabled

Two trips on cross zone

37

5/4

Disabled

Required

Keypad sounds on cross zone trip 39

5

Disabled

Cross zoning

Zone type characteristic

111

3/4

Disabled

Programmable cross zoning
time

Cross zone time

40

6

5 minutes

Allowed

Swinger shutdown

Swinger shutdown count

38

n/a

n/a

For all nonfire zones, shut
down at 1 to 2 trips

Swinger shutdown disable

Swinger shutdown count

38

n/a

Enabled for 1 trip

Allowed

Fire alarm verification

Fire alarm verification time

40

9

Enabled for 1 trip

Required (depends on
panel and sensors)

Call waiting cancel

Must be programmed as part of
the phone number

0 n/a

n/a

Required

(depends

on

user phone line)

Recent closing

23

3/7

Enabled

Exit error

23

3/8

Enabled

Default changes (from prior
versions):

Power up delay

40

3

60 seconds

a> Refer to your keypad installation manual.

b> Combined abort window time and entry delay must not exceed one minute.

10

NX-4V2 Control Panel Installation Instructions