Uninterruptible Power Supply (UPS)

B-2

Figure B-1. Connecting EM to UPS

Configuring COM Port for UPS

After the UPS has been connected to the COM2 port, the COM2 port must be
configured for UPS Management. To configure the COM2 port for UPS
Management, follow the steps below.

1.

Connect the terminal or PC used for local management to the COM1 port on
the Environmental Module (EM) and press RETURN until the Slot Selection
Screen displays.

2.

At the Slot Selection Screen, enter 0 (zero) to display the EM Configuration
Screen.

3.

At the EM Configuration Screen, cursor to the Application Field for the
COM2 port.

4.

Using the space bar, toggle to the UPS option.

5.

Using the tab key, tab to the SAVE option and press RETURN.

If you need additional information about configuring the COM ports, refer to the
Local Management User’s Guide

.

9C3001