WARNING!!

The unit must have adequate structural

support or the equipment or building

could be damaged.


WARNING!!

Screw or weld the unit’s base to the curb

to avoid damage to the equipment.

WARNING!!

The curb and unit must be leveled or the

unit may leak or be damaged.

Accessories

Intake and discharge accessories are shipped loose and unassembled. When attaching the accessories
to the unit use gasket, caulk, and #10 sheet metal screws on all seams. All accessories must be level.

WARNING!!

Use gasket, caulk, and #10 sheet metal screws on

all component intersections. Leaking may result if

the intersections are not completed properly.

WARNING!!

The accessories must be level and support legs

attached to the hood and solid part of the roof.

Equipment that is not level or properly supported

may leak or be damaged.

Split Units

1. Apply weather-proof gasket to the seam of the vertical or horizontal unit
2. Use provided fasteners to secure the seam of the unit using the provided pre-punched holes

a. Horizontal units internal channels and a formed frame
b. Vertical units have angles on the outside of the casing

3. Apply silicone to the outside edge of the seam
4. Field wire the discharge air sensor using a minimum 22 gauge wire
5. Mount the high temperature limit bulb to the blower housing
6. Mount the (optional) freeze control sensor to the blower housing